2020-01-08 15:30:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120386
 1/8/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW
 ADDITIONS TO THE BUILDING- SECTION C502.1 AND C101.5.1
 FBC EC.
  
 3) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL EXSITNG AND NEW ROOMS
 AND SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR.
  
 4) SHEET M-1.0: INDICATE HOW THE REQUIRED OUTSIDE AIR
 IS BEING PROVIDED TO THE EXISTING AND NEW ROOMS AND
 SPACES- SEE SECTION 402 & 403 FBC M. PLEASE NOTE THAT
 PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS ARE
 REQUIRED FOR O/A INTAKE DUCTS- SECTION C403.2.4.3 FBC
 EC.
  
 5) M-1.0: RETURN AIR SYSTEMS NOT SHOWN- SECTION 601.6
 FBC M.
  
 6) M-1.0 & M-2.0: THE AC EQUIPMENT IS INCORRECTLY
 INDICATING THE SYSTEMS ARE FOR 2ND FLOOR BEDROOMS-
 PLEASE CORRECT.
  
 7) M-1.0 & M-2.0: THE 1600 CFM CAPACITIES FOR THE 4-TON
 SYSTEMS SHOWN IN THE SCHEDULE ARE UNDERIZED COMPARED TO
 THE CFMS BEING DISTRIBUTED ON THE AC LAYOUT PLAN. THESE
 APPEAR TO BE MUCH LARGER SYSTEMS WHICH WILL ALSO
 REQUIRE DUCT SMOKE DETECTORS ION THE MAIN SUPPLY DUCTS-
 SECTION 606.2.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT REVIEW
 OF RESUBMITTED CORRECTED PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. ADDITIONAL COMMENTS.
  