| 2019-12-18 12:46:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET TS 1 - UNDER PROJECT INFORMATION THERE IS AN |
| | INDICATION OF CITY OF DELRAY BEACH. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 2) SHEET TS 1 - UNDER PROJECT INFORMATION/OCCUPANCY |
| | CLASSIFICATION THERE IS AN INDICATION OF ASSEMBY - |
| | RESTURAUNT. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 3) SHEET A 1.3 - THERE ARE INDICATIONS OF CLASSROOMS |
| | WHICH IS EDUCATIONAL PER THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | IS THIS A MIXED OR SEPARATED OCCUPANCY? |
| | |
| | ARE THE CLASSROOMS JUST FOR SUNDAY ATTENDANCE? |
| | |
| | PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | PLEASE REVIEW AND CLARIFY AND PROVIDE APPLICABLE |
| | CONSTRUCTION SEPARATION DETAILS. OR JUSTIFY WITH |
| | SEPECIFIC CODE REFERENCES AND DETAILED NARRATIVE. |
| | |
| | |
| | 3A) ARE THE CLASSROOMS JUST FOR SUNDAY ATTENDANCE? |
| | |
| | PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION |
| | |
| | 6.1.3 EDUCATIONAL. FOR REQUIREMENTS, SEE CHAPTERS 14 |
| | AND 15. |
| | 6.1.3.1* DEFINITION ? EDUCATIONAL OCCUPANCY. AN |
| | OCCUPANCY USED |
| | FOR EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY |
| | SIX OR MORE |
| | PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE THAN 12 |
| | HOURS PER WEEK. |
| | 6.1.3.2 OTHER OCCUPANCIES. OTHER OCCUPANCIES ASSOCIATED |
| | WITH |
| | EDUCATIONAL INSTITUTIONS SHALL BE IN ACCORDANCE WITH |
| | THE APPROPRIATE PARTS |
| | OF THIS CODE. |
| | 6.1.3.3 INCIDENTAL INSTRUCTION. IN CASES WHERE |
| | INSTRUCTION IS INCIDENTAL |
| | TO SOME OTHER OCCUPANCY, THE SECTION OF THIS CODE |
| | GOVERNING SUCH OTHER |
| | OCCUPANCY SHALL APPLY. |
| | |
| | PLEASE A DETAILED NARRATIVE OF CLASSROMM FUNCTION. |
| | |
| | |
| | 4) SHEET A 2.1 - TWO DOORS, 105 & 106 OPEN INTO THE |
| | EXIT CORRIDOR. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 5) SHEET A 2.1 & S 2.0 - THE SMALL CORRIDOR SHOWS |
| | DIFFERENT MEASURMENTS, 3'11" AND 4'1" RESPECTIVELY AND |
| | 5'11" & 6'1". |
| | |
| | WHICH SET OF MEASURMENTS IS CORRECT? |
| | |
| | PLEASE CORRECT OR JUSTIFY. |
| | |
| | |
| | 6) SHEET A 2.1 - THE DOOR SCHEDULE DOES NOT INDICATE |
| | HARDWARE, EXIT HARDWARE(PANIC), LOCKS/LATCHES, ETC. |
| | |
| | PER NFPA 101, CH 12 & 7 |
| | |
| | 12.2.2 MEANS OF EGRESS COMPONENTS. |
| | 12.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF |
| | EGRESS |
| | SHALL BE LIMITED TO THE TYPES DESCRIBED IN 12.2.2.2 |
| | THROUGH 12.2.2.12. |
| | 12.2.2.2 DOORS. |
| | 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 12.2.2.2.2 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF |
| | 300 OR LESS IN |
| | MALLS (SEE 36.4.4.4.2(4) SHALL BE PERMITTED TO HAVE |
| | HORIZONTAL OR VERTICAL |
| | SECURITY GRILLES OR DOORS COMPLYING WITH 7.2.1.4.1(3) |
| | ON THE MAIN |
| | ENTRANCE/EXITS. |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE. |
| | |
| | |
| | 7) SHEET S 3.0 - THE ROOF TRUSS DESIGN IS UNCLEAR. |
| | |
| | PLEASE CLARIFY AND IF APPLICABLE PROVIDE A LIGHTWEIGHT |
| | FRAME SIGN PER STATE LAW. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |