Plan Review Notes
Plan Review Notes For Permit 19120386
Permit Number 19120386
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-18 12:46:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET TS 1 - UNDER PROJECT INFORMATION THERE IS AN
 INDICATION OF CITY OF DELRAY BEACH.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) SHEET TS 1 - UNDER PROJECT INFORMATION/OCCUPANCY
 CLASSIFICATION THERE IS AN INDICATION OF ASSEMBY -
 RESTURAUNT.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET A 1.3 - THERE ARE INDICATIONS OF CLASSROOMS
 WHICH IS EDUCATIONAL PER THE FLORIDA FIRE PREVENTION
 CODE.
  
 IS THIS A MIXED OR SEPARATED OCCUPANCY?
  
 ARE THE CLASSROOMS JUST FOR SUNDAY ATTENDANCE?
  
 PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE REVIEW AND CLARIFY AND PROVIDE APPLICABLE
 CONSTRUCTION SEPARATION DETAILS. OR JUSTIFY WITH
 SEPECIFIC CODE REFERENCES AND DETAILED NARRATIVE.
  
  
 3A) ARE THE CLASSROOMS JUST FOR SUNDAY ATTENDANCE?
  
 PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION
  
 6.1.3 EDUCATIONAL. FOR REQUIREMENTS, SEE CHAPTERS 14
 AND 15.
 6.1.3.1* DEFINITION ? EDUCATIONAL OCCUPANCY. AN
 OCCUPANCY USED
 FOR EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY
 SIX OR MORE
 PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE THAN 12
 HOURS PER WEEK.
 6.1.3.2 OTHER OCCUPANCIES. OTHER OCCUPANCIES ASSOCIATED
 WITH
 EDUCATIONAL INSTITUTIONS SHALL BE IN ACCORDANCE WITH
 THE APPROPRIATE PARTS
 OF THIS CODE.
 6.1.3.3 INCIDENTAL INSTRUCTION. IN CASES WHERE
 INSTRUCTION IS INCIDENTAL
 TO SOME OTHER OCCUPANCY, THE SECTION OF THIS CODE
 GOVERNING SUCH OTHER
 OCCUPANCY SHALL APPLY.
  
 PLEASE A DETAILED NARRATIVE OF CLASSROMM FUNCTION.
  
  
 4) SHEET A 2.1 - TWO DOORS, 105 & 106 OPEN INTO THE
 EXIT CORRIDOR.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
 5) SHEET A 2.1 & S 2.0 - THE SMALL CORRIDOR SHOWS
 DIFFERENT MEASURMENTS, 3'11" AND 4'1" RESPECTIVELY AND
 5'11" & 6'1".
  
 WHICH SET OF MEASURMENTS IS CORRECT?
  
 PLEASE CORRECT OR JUSTIFY.
  
  
 6) SHEET A 2.1 - THE DOOR SCHEDULE DOES NOT INDICATE
 HARDWARE, EXIT HARDWARE(PANIC), LOCKS/LATCHES, ETC.
  
 PER NFPA 101, CH 12 & 7
  
 12.2.2 MEANS OF EGRESS COMPONENTS.
 12.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF
 EGRESS
 SHALL BE LIMITED TO THE TYPES DESCRIBED IN 12.2.2.2
 THROUGH 12.2.2.12.
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 12.2.2.2.2 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF
 300 OR LESS IN
 MALLS (SEE 36.4.4.4.2(4) SHALL BE PERMITTED TO HAVE
 HORIZONTAL OR VERTICAL
 SECURITY GRILLES OR DOORS COMPLYING WITH 7.2.1.4.1(3)
 ON THE MAIN
 ENTRANCE/EXITS.
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE.
  
  
 7) SHEET S 3.0 - THE ROOF TRUSS DESIGN IS UNCLEAR.
  
 PLEASE CLARIFY AND IF APPLICABLE PROVIDE A LIGHTWEIGHT
 FRAME SIGN PER STATE LAW.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709