| Plan Review Notes For Permit 19120386 |
| Permit Number |
19120386 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-08 08:40:32 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E1.0 | | | | | | 1) GFCI REQUIRED FOR OUTLETS INSTALLED WITHIN 6' OF | | | SINKS. 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER | | | PROTECTION FOR PERSONNEL (B) OTHER THAN DWELLING UNITS. | | | (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 | | | M (6 FT) OF THE OUTSIDE EDGE OF THE SINK. | | | | | | PAGE E2.0 | | | | | | 2) C405.2LIGHTING CONTROLS (MANDATORY). LIGHTING | | | SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS SPECIFIED IN | | | SECTIONS C405.2.1, C405.2.2, C405.2.3, C405.2.4 AND | | | C405.2.5. | | | | | | 3) ALL SYMBOLS NOT SHOWN ON PLANS SM? | | | | | | PAGE E3.0 | | | | | | 4) RISER DIAGRAM SHOWS 300 AMPERE SERVICE WITH 2/0 | | | CONDUCTORS. | | | | | | 5) FAULT CURRENT RATING FOR SERVICE, HOW DID YOU | | | CALCULATE THE AIC RATING? | | | | | | 6) LOAD CALCULATION LIGHTING LOAD NOT PER 220.12. | | | CHURCH 1VA SCHOOL 3VA PER SQFT | | | | | | |
|