2020-01-08 08:40:32FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E1.0
  
 1) GFCI REQUIRED FOR OUTLETS INSTALLED WITHIN 6' OF
 SINKS. 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL (B) OTHER THAN DWELLING UNITS.
 (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8
 M (6 FT) OF THE OUTSIDE EDGE OF THE SINK.
  
 PAGE E2.0
  
 2) C405.2LIGHTING CONTROLS (MANDATORY). LIGHTING
 SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS SPECIFIED IN
 SECTIONS C405.2.1, C405.2.2, C405.2.3, C405.2.4 AND
 C405.2.5.
  
 3) ALL SYMBOLS NOT SHOWN ON PLANS SM?
  
 PAGE E3.0
  
 4) RISER DIAGRAM SHOWS 300 AMPERE SERVICE WITH 2/0
 CONDUCTORS.
  
 5) FAULT CURRENT RATING FOR SERVICE, HOW DID YOU
 CALCULATE THE AIC RATING?
  
 6) LOAD CALCULATION LIGHTING LOAD NOT PER 220.12.
 CHURCH 1VA SCHOOL 3VA PER SQFT
  
  