2020-02-19 07:06:311. SURVEY IS MORE THAN 3 YEARS OLD. THERE HAS BEEN
 CONSTRUCTION ON THE PROPERTY (NEW BUILDING) SINCE THE
 SURVEY WAS COMPLETED.
 2. NOTE 8 ON THE SURVEY NEEDS TO BE UPDATED. REVISED
 FEMA MAPS WERE ISSUED A FEW YEARS AGO.
 3. THE SURVEY AND ENGINEERING PLANS USE NGVD1929. THE
 DRAINAGE CALCULATIONS REFERENCE NAVD1988.
 4. I COULD NOT FIND SECTION A-A OR SECTION B-B ON THE
 PGD PLAN (SHEET CE1).
 5. THE SIDE SLOPES AND BOTTOM WIDTH OF THE SWALE NEED
 TO BE DIMENSIONED ON THE TWO SECTIONS ON PGD PLAN
 (SHEET CE1).
 6. THE DRIVE LANE BETWEEN THE TWO BUILDINGS WILL FLOOD
 BEFORE THE DETENTION PONDS OVER TOP AND DRAIN TO THE
 ROAD.
 7. DRAINAGE CALCULATIONS NEED TO PROVIDE PRE- VS POST-
 DISCHARGE OR RUNOFF CALCULATIONS LEAVING THE SITE.
 8. CONSIDER REDUCING THE DEPTH OF THE PARKING SPACES
 AND PROVIDE TWO FEET OF OVERHANG. WHEEL STOPS WILL NOT
 BE NEEDED IF RAISED CURB IS USED.
  
 NOTE THE NAVD1988/NGVD1929 CONVERSION EQUATION IS NOT
 NEEDED IF NGVD1929 (CITY?S OFFICIAL VERTICAL DATUM) IS
 USED.
  