| Plan Review Notes For Permit 19120336 |
| Permit Number |
19120336 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-10 08:27:46 | | | | 1ST REVIEW FBC-2017 BUILDING | | | PERMIT 19120336 | | | 12/10/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SELECT A SYSTEM TO BE INSTALLED AS INDICATED. | | | THE SYSTEMS ARE SHOWN IN THE NOA FROM PAGES 9-65. | | | | | | 2) PLEASE SEE LIMITATION #7 ON PAGE 67: INCREASED | | | FASTENER DENSITIES AT PERIMETER AND CORNER AREAS | | | REQUIRED. PROVIDE CALCULATIONS PREPARED AND SIGNED AND | | | SEALED BY A FL. REGISTERED PROFESSIONAL ENGINEER, | | | ARCHITECT, OR REGISTERED ROOF CONSULTANT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|