| Plan Review Notes For Permit 19120313 |
| Permit Number |
19120313 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-05-06 16:31:36 | PLAN REVIEW - MECHANICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? BUILDING - PX3169 | | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. | | | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1) FBC B 107.1 PLEASE PROVIDE TIE DOWN DETAILS FOR THE | | | ROOF TOP UNIT CONNECTIONS. (ROOFTOP STAND SUBJECT TO | | | WIND LOADS, DESIGN PROFESSIONALS SIGNATURE AND SEAL | | | REQUIRED) | | | | | | 2) FBC B 107.1 PLEASE PROVIDE A LETTER SIGNED BY THE | | | OWNER ACKNOWLEDGING THAT THE REPLACEMENT OF THE ROOF | | | TOP PACKAGE UNIT MAY JEOPARDIZE THE INTEGRITY OF THE | | | ROOF OR PROVIDE A ROOFING SUB-PERMIT (NOT ADDRESSED) | | | | | | |
|