| 2020-05-06 16:42:41 | PLAN REVIEW - ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 |
| | (SCOPE OF WORK REDUCED, VALUE OK) |
| | |
| | 2. PROVIDE LOCATION OF ELECTRICAL SERVICE AND PANEL TO |
| | CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1 |
| | CORRECTED |
| | |
| | 3. ANY WORK THAT IS SHOWN AS EXISTING THAT WAS DONE |
| | WITHOUT A PERMIT SHOLD BE SHOWN AS NEW INSTALLATION. |
| | PROVIDE CLARIFICATION AS TO WHAT WORK WAS COMPLETED |
| | WITHOUT A PERMIT. WPB FBC 107.2.1 |
| | CORRECTED |
| | |
| | NEW COMMENT: |
| | |
| | 4. SHOW NEW WATER HEATER ON PANEL SCHEDULE. IDENTIFY |
| | CKT., POLE/TRIP AND WIRE SIZE. |
| | PANEL SCHEDULE: |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | |
| | |
| | |
| | |