| Plan Review Notes For Permit 19120313 |
| Permit Number |
19120313 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-24 10:56:51 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1) FBC B 107.1 PLEASE PROVIDE TIE DOWN DETAILS FOR THE | | | ROOF TOP UNIT CONNECTIONS. | | | | | | 2) FBC B 107.1 PLEASE PROVIDE A LETTER SIGNED BY THE | | | OWNER ACKNOWLEDGING THAT THE REPLACEMENT OF THE ROOF | | | TOP PACKAGE UNIT MAY JEOPARDIZE THE INTEGRITY OF THE | | | ROOF OR PROVIDE A ROOFING SUB-PERMIT. |
|