2020-03-14 14:51:3403/14/20 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT
 WILL BE DONE ON THIS REVIEW PROCESS, IF NOT TO CODE, IT
 MAY NEED TO BE BOUT UP TO CODE COMPLIANCE.
  
 2. GAS APPLIANCES (WATER HEATER) SHALL NOT BE IN
 PROHIBITED LOCATION AS UNLESS IT COMPLIES WITH 2017 FBC
 RES. SEC. G2406.2.
  
 3. PLEASE SHOW IN DETAIL THE VENTING, THE COMBUSTION
 AIR INTAKE IN ACCORDANCE WITH 2017 FBC RES. SEC.
 G2407.1.
  
 4. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 5. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 7. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS,
 BTU'S OF GENERATOR AND REGULATORS (IF NEEDED) ON
 ISOMETRIC PER THE 2017 FBC FG SEC. 409.4.
  
 8. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
 6. SUBMIT COPIES OF THE CORRECT SIZING TABLE USED IN
 THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH
 SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES
 OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF
 THIS SYSTEM PER THE 2017 FBC FG SEC. 402.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 8. IF GAS HEATER IS NOT TO CODE INSIDE IT MAY BE CHANGE
 TO AN OUTSIDE UNIT AND A NEW REVIEW ALONG WITH
 SUPPORTING DOCUMENTATION WILL BE REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  