| Date |
Text |
| 2020-08-19 11:59:46 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120254 |
| | ADD: 101 N. CLEMATIS ST. SUITE 417 |
| | CONT: TOWN MANAGEMENT SERVICES |
| | TEL: 954-292-2956 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. AUGUST 194TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. COMP2ND REVIEW, SEMI-COMPLIED. THE |
| | SUBMITTED PLANS ARE THE WORK OF EDGAR V. DUENAS P. E. # |
| | 57831. PLEASE NOTE THE SGNATURE AND SEAL ON THESE PLANS |
| | WOULD BE FOR A PAAER SET OF PLANS, NOT DIGITAL PLANS. |
| | |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES), |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | DIGITALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 1ST ROUND COMMENTS. 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| | CODE SECTION 107.3.4.3. CERTIFICATION BY CONTRACTOR. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE |
| | YOU CANNOT CREATE PLANS YOU AREN?T LICENSED IN. |
| | |
| | |
| | 3) SEMI-COMPLIED. THIS REVIEW A PROFLEX PRODUCT MSC A |
| | SALES BROCHURE WAS YP LOADED NOT ACTUAL TEST REPORTS. |
| | PLEASE NOTE ON THE SALES BROCHURE UNDER THE TEST DATA |
| | THE RESULTS ARE GIVEN FOR A 8 INCH CONCRETE SLAB WITH |
| | DROPPED CEILING WITH INSULATION. |
| | |
| | THE CITY OF W. P. B. BUILDING DIVISION DOES HAVE ACTUAL |
| | TEST REPORTS FOR A SIMILAR PROFLEX PRODUCT SUPER SIM 90 |
| | ON A 6 INCH CONCRETE SLAB, NO DROPPED CEILING: |
| | IIC=50 ASTM -E492 |
| | STC=52 ASTM E-90 |
| | FLAME=0 ASTM E-84 |
| | SMOKE= ASTM E-84 |
| | IF THIS PRODUCTIS SOMETHING YOU WOULD LIKE TO USE STATE |
| | SO ON THE PLANS, NO TEST REPORTS REQUIRED SINCE THE |
| | CITY HAS THESE REPORTS. |
| | |
| | . SHEET A-1 DOES INDICATE 1/2 INCH DURAROCK TO BE |
| | SECURED TO THE CONCRETE DECK AND THERE IS A NOTE SEE |
| | ATTACHMEENTS FOR SOUND PROOFING BUT THERE IS NO FILES |
| | ATTACHED IN ANY FOLDERS OR TO THE SUBMITTED PLANS. YOU |
| | MAY WANT TO CALL THE LIBRIAN LAURA MARCHANT TO DISCUSS |
| | HOW TO ATTACH THESE DOCUMENTS, 561-805-6658. |
| | THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD AND |
| | TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR THE |
| | INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS, WOOD |
| | AND TILE FLOORING. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 3A 2ND REQUEST. ) FBC-B 2017 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| | |
| | 3B) 2ND REQUEST. FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2017 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |