Plan Review Notes
Plan Review Notes For Permit 19120254
Permit Number 19120254
Review Stop B
Sequence Number 3
Notes
Date Text
2020-08-19 11:59:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120254
 ADD: 101 N. CLEMATIS ST. SUITE 417
 CONT: TOWN MANAGEMENT SERVICES
 TEL: 954-292-2956
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. AUGUST 194TH/ 2020
 ACTION: DENIED
  
 1-2) COMPLIED. COMP2ND REVIEW, SEMI-COMPLIED. THE
 SUBMITTED PLANS ARE THE WORK OF EDGAR V. DUENAS P. E. #
 57831. PLEASE NOTE THE SGNATURE AND SEAL ON THESE PLANS
 WOULD BE FOR A PAAER SET OF PLANS, NOT DIGITAL PLANS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1ST ROUND COMMENTS. 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION 107.3.4.3. CERTIFICATION BY CONTRACTOR.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE
 YOU CANNOT CREATE PLANS YOU AREN?T LICENSED IN.
  
  
 3) SEMI-COMPLIED. THIS REVIEW A PROFLEX PRODUCT MSC A
 SALES BROCHURE WAS YP LOADED NOT ACTUAL TEST REPORTS.
 PLEASE NOTE ON THE SALES BROCHURE UNDER THE TEST DATA
 THE RESULTS ARE GIVEN FOR A 8 INCH CONCRETE SLAB WITH
 DROPPED CEILING WITH INSULATION.
  
 THE CITY OF W. P. B. BUILDING DIVISION DOES HAVE ACTUAL
 TEST REPORTS FOR A SIMILAR PROFLEX PRODUCT SUPER SIM 90
 ON A 6 INCH CONCRETE SLAB, NO DROPPED CEILING:
 IIC=50 ASTM -E492
 STC=52 ASTM E-90
 FLAME=0 ASTM E-84
 SMOKE= ASTM E-84
 IF THIS PRODUCTIS SOMETHING YOU WOULD LIKE TO USE STATE
 SO ON THE PLANS, NO TEST REPORTS REQUIRED SINCE THE
 CITY HAS THESE REPORTS.
  
 . SHEET A-1 DOES INDICATE 1/2 INCH DURAROCK TO BE
 SECURED TO THE CONCRETE DECK AND THERE IS A NOTE SEE
 ATTACHMEENTS FOR SOUND PROOFING BUT THERE IS NO FILES
 ATTACHED IN ANY FOLDERS OR TO THE SUBMITTED PLANS. YOU
 MAY WANT TO CALL THE LIBRIAN LAURA MARCHANT TO DISCUSS
 HOW TO ATTACH THESE DOCUMENTS, 561-805-6658.
 THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD AND
 TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR THE
 INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS, WOOD
 AND TILE FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 3A 2ND REQUEST. ) FBC-B 2017 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 3B) 2ND REQUEST. FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2017 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved