Plan Review Notes
Plan Review Notes For Permit 19120254
Permit Number 19120254
Review Stop P
Sequence Number 2
Notes
Date Text
2020-06-01 12:53:222ND REVIEW FBC-2017 PLUMBING
 PERMIT- 19120254
 6/1/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW REQUESTING FAIR
 HOUSING ACT GUIDELINES BATHROOM DESIGN SPECIFICATIONS
 WAS NOT ADDRESSED. AS STATED IN THE COMMENT, BATHROOMS
 CONSTRUCTED UNDER THE FAIR HOUSING ACT SHALL BE
 DESIGNED AS EITHER TYPE A OR B. REVISE THE NOTES AND
 DETAILS ON SHEET A.2/P.1 TO CLARIFY THE SCOPE OF WORK
 PERTAINING TO THE SHOWER IN THE MASTER BATH AND THE NEW
 WATER HEATER. BASED ON THE DEMO PLAN AND THE NEW
 DRAWINGS, THE PROJECT APPEARS TO BE A CONVERSION OF A
 TUB AND SHOWER COMPARTMENT INTO A SHOWER COMPARTMENT,
 AND A NEW WATER HEATER AT A NEW LOCATION.
 FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE
 BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED. THE PLAN IS INDICATING THE CONVERSION OF A
 BATHTUB TO A SHOWER IN THE MASTER BATH. PROVIDE AN
 ENLARGED DIMENSIONED DRAWING OF THE BATHROOM SHOWING
 THE REQUIRED CLEAR FLOOR SPACE DIAGRAM FOR THE NEW
 SHOWER. PLEASE SEE REQUIREMENT 7 CONTAINED IN THE
 GUIDELINES AND FIGURE 5, AND FIGURES 7A, 7C, & 7D FOR
 GUIDANCE. CONCERNING THE SHOWER GRAB BAR AND WALL HUNG
 BENCH SEAT REINFORCEMENTS SHALL BE INSTALLED IN THE
 SHOWER WALLS TO ACCOMMODATE FUTURE INSTALLATIONS.
 PLEASE PROVIDE DIMENSIONED ELEVATION VIEWS SHOWING THE
 LOCATIONS OF THE WALL REINFORCEMENTS.
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 2) SHEET A.2/P.1: CONCERNING THE NEW SHOWER DRAIN
 OUTLET SHOW COMPLIANCE WITH ITEMS A, B, & C LISTED
 BELOW.
 A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
 B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE
 FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING
 STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A
 NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET-
 SECTION 1-07.2.1 WPB.
 C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 3) A.2/P.1: PROVIDE COMPLETE SANITARY AND WATER RISER
 DRAWINGS FOR THE CONVERTED MASTER BATH THAT SHOWS
 POINTS OF CONNECTIONS TO THE EXISTING DWV AND WATER
 SUPPLY SYSTEMS- SECTIONS 107.2.1 & 107.3.5.1.3 WPB.
  
 4) A.2/P.1: SHOWER DETAIL: THE SLOPE OF THE SHOWER PAN
 LINER SHALL BE 1/4" PER FT., NOT 1/8" AS INDICATED IN
 THE DETAIL- SEE SECTION 417.5.2 FBC P.
  
 4) A.2/P.1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE
 ON THE PLAN AND SUBMIT MANUFACTURER?S SPECIFICATIONS
 AND INSTALLATION GUIDELINES- SECTION 502.1 FBC P, AND
 SECTION C404.2 FBC EC.
  
 5) A.2/P.1: SHOW THE TYPE AND SIZE OF PAN DRAIN PIPE
 FOR NEW WATER HEATER PAN DRAIN PIPE AND IT'S
 TERMINATION LOCATION- SECTIONS 504.7.1 & 504.7.2 FBC P.
  
 6) A.2/P.1: A 3" DRAIN IS REQUIRED FOR THE NEW WASHING
 MACHINE PER SECTION 406.2 FBC P. PLEASE CORRECT NOTE #4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected].
  