Plan Review Notes
Plan Review Notes For Permit 19120254
Permit Number 19120254
Review Stop M
Sequence Number 2
Notes
Date Text
2020-05-21 10:04:40PLAN DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN FOR NEW AIR
 CONDITIONING.
 SECTION 107 FBC 2017
 2) REFER TO SECTION 307 FBC (M) 2017 SHOW CONDENSATE
 LINE FOR
 AIR CONDITIONING ON PLAN.
 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES EXCEPTION
 #1
 (DRYER SUBDUCT) FBC (M) 2017
 4) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 INCLUDING
 DOORS 2017 FBC(M)
 5) REFER TO SECTION 402 OR 403 FBC(M) 2017 PROVIDE
 CALCULATIONS
 FOR OUTSIDE AIR.
 6) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS. OUTDOOR
 AIR INTAKE
 AND EXHAUST DAMPERS. 2017 FLORIDA ENERGY CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676