| Plan Review Notes For Permit 19120254 |
| Permit Number |
19120254 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-05-21 10:04:40 | PLAN DENIED | | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN FOR NEW AIR | | | CONDITIONING. | | | SECTION 107 FBC 2017 | | | 2) REFER TO SECTION 307 FBC (M) 2017 SHOW CONDENSATE | | | LINE FOR | | | AIR CONDITIONING ON PLAN. | | | 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES EXCEPTION | | | #1 | | | (DRYER SUBDUCT) FBC (M) 2017 | | | 4) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S | | | INCLUDING | | | DOORS 2017 FBC(M) | | | 5) REFER TO SECTION 402 OR 403 FBC(M) 2017 PROVIDE | | | CALCULATIONS | | | FOR OUTSIDE AIR. | | | 6) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS. OUTDOOR | | | AIR INTAKE | | | AND EXHAUST DAMPERS. 2017 FLORIDA ENERGY CODE | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|