Plan Review Notes
Plan Review Notes For Permit 19120254
Permit Number 19120254
Review Stop M
Sequence Number 1
Notes
Date Text
2019-12-27 08:46:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL PLAN SHOWING ALL ALTERATIONS TO
 THE EXISTING HVAC SYSTEMS. THE DEMO PERMIT #18111262
 INDICATES THAT THE AIR HANDLER AND DRYER HAVE BEEN
 RELOCATED- SECTION 107.2.1 WPB.
  
 A) SHOW POINTS OF AC SUPPLY AND RETURN DUCT CONNECTIONS
 AND NEW DUCT RUNS- SECTION 603 FBC M.
 B) SHOW THE NEW DRYER EXHAUST DUCT RUN AND INDICATE THE
 TOTAL RUN LENGTH- SECTION 504.8.4.FBC M. PLEASE NOTE
 THAT MAKEUP AIR MAY BE REQUIRED- SECTION 504.6.
 C) SHOW NEW O/A DUCT CONNECTION AND REQUIRED DAMPER
 (NOT APPLICABLE IF NATURAL VENTILATION OPENINGS ARE
 BEING USED)- SECTIONS 402 & 403 FBC M, & SECTION
 C403.2.4.3 FBC EC.
 D) SHOW A FRONT VIEW OF THE AIR HANDLER IN THE NEW
 CLOSET INDICATING REQUIRED CLEARANCES AROUND THE UNIT,
 AND NEW CONDENSATE PIPING RUN. PLEASE NOTE THAT IF A
 NEW LOUVERED DOOR IS BEING INSTALLED FOR RETURN AIR, IT
 SHALL BE NONCOMBUSTIBLE- 602.1 FBC M.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER
 PER SECTION 504.1 FBC M, AND THE NEW COOKING
 APPLIANCES- SECTION 917.1 FBC M.
  
 3) SUBMIT MANUFACTUTRER'S SPECIFICATIONS FOR THE
 RECIRCULATING KITCHEN HOOD- SECTION 505.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  