| 2019-12-27 08:46:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A MECHANICAL PLAN SHOWING ALL ALTERATIONS TO |
| | THE EXISTING HVAC SYSTEMS. THE DEMO PERMIT #18111262 |
| | INDICATES THAT THE AIR HANDLER AND DRYER HAVE BEEN |
| | RELOCATED- SECTION 107.2.1 WPB. |
| | |
| | A) SHOW POINTS OF AC SUPPLY AND RETURN DUCT CONNECTIONS |
| | AND NEW DUCT RUNS- SECTION 603 FBC M. |
| | B) SHOW THE NEW DRYER EXHAUST DUCT RUN AND INDICATE THE |
| | TOTAL RUN LENGTH- SECTION 504.8.4.FBC M. PLEASE NOTE |
| | THAT MAKEUP AIR MAY BE REQUIRED- SECTION 504.6. |
| | C) SHOW NEW O/A DUCT CONNECTION AND REQUIRED DAMPER |
| | (NOT APPLICABLE IF NATURAL VENTILATION OPENINGS ARE |
| | BEING USED)- SECTIONS 402 & 403 FBC M, & SECTION |
| | C403.2.4.3 FBC EC. |
| | D) SHOW A FRONT VIEW OF THE AIR HANDLER IN THE NEW |
| | CLOSET INDICATING REQUIRED CLEARANCES AROUND THE UNIT, |
| | AND NEW CONDENSATE PIPING RUN. PLEASE NOTE THAT IF A |
| | NEW LOUVERED DOOR IS BEING INSTALLED FOR RETURN AIR, IT |
| | SHALL BE NONCOMBUSTIBLE- 602.1 FBC M. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER |
| | PER SECTION 504.1 FBC M, AND THE NEW COOKING |
| | APPLIANCES- SECTION 917.1 FBC M. |
| | |
| | 3) SUBMIT MANUFACTUTRER'S SPECIFICATIONS FOR THE |
| | RECIRCULATING KITCHEN HOOD- SECTION 505.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |