| 2020-01-06 06:35:15 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120254 |
| | ADD: 101 N. CLEMATIS ST. SUITE 417 |
| | CONT: TOWN MANAGEMENT SERVICES |
| | TEL: 954-292-2956 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY, JAN.6TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION |
| | 107.3.4.3. CERTIFICATION BY CONTRACTOR. THE CONTRACTOR |
| | (QUALIFIER) THAT CREATED / DRAWN THE SET OF PLANS WILL |
| | NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. |
| | PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE |
| | NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS |
| | DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE YOU CANNOT |
| | CREATE PLANS YOU AREN?T LICENSED IN. |
| | |
| | 2) FLOOR PLAN NOTE 3 INDICATES MINOR FRAMING. IDENTIFY |
| | THE MINIMUM BUILDING TYPE OF CONSTRUCTION TABLE 504.3, |
| | TABLE 504.4 & 506.2 OF THE 2017 FBC-B. THERE IS NO |
| | PLANS IDENTIFYING THE LOCATION OF THE NEW FRAMING, |
| | WALLS, DROPPED CEILINGS ETC. FOR WALLS ARE THEY BEARING |
| | OR NON-BEARING WALLS. PLEASE IDENTIFY THE FRAMING |
| | MEMBERS BY USAGE, (WALL OR DROPPED CEILING) SIZE OF |
| | MATERIAL, C-STUDS, JOIST, TRACK, CHANNEL AND OR FURRING |
| | CHANNEL (HIGH HAT), GAUGE OF MATERIAL/ THICKNESS, |
| | FLANGE WIDTH, SPACING C/C, FOR WALLS LENGTH OF STUD, |
| | AND FOR WALLS THE DEFLECTION LIMITATION SEE TABLE |
| | 1604.3.OF THE 2017 FBC-B AND THICKNESS OF DRYWALL, IS |
| | THE WALL FIRE RATED. FOR DROPPED CEILINGS AND SOFFITS, |
| | TYPE OF MATERIALS C-STUDS, JOIST, TRACK, CHANNEL AND OR |
| | FURRING CHANNEL (HIGH HAT), GAUGE OF MATERIAL/ |
| | THICKNESS, FLANGE WIDTH, SPACING C/C, SPAN, MID-POINT |
| | SUPPORT, THICKNESS OF DRYWALL. |
| | |
| | 3) THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD |
| | AND TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR |
| | THE INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS, |
| | WOOD AND TILE FLOORING. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| | |
| | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |