Plan Review Notes
Plan Review Notes For Permit 19120254
Permit Number 19120254
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-06 06:35:152017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120254
 ADD: 101 N. CLEMATIS ST. SUITE 417
 CONT: TOWN MANAGEMENT SERVICES
 TEL: 954-292-2956
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY, JAN.6TH/ 2020
 ACTION: DENIED
  
 1) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION
 107.3.4.3. CERTIFICATION BY CONTRACTOR. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DRAWN THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN. UNLESS YOU ARE LICENSED IN THAT TRADE YOU CANNOT
 CREATE PLANS YOU AREN?T LICENSED IN.
  
 2) FLOOR PLAN NOTE 3 INDICATES MINOR FRAMING. IDENTIFY
 THE MINIMUM BUILDING TYPE OF CONSTRUCTION TABLE 504.3,
 TABLE 504.4 & 506.2 OF THE 2017 FBC-B. THERE IS NO
 PLANS IDENTIFYING THE LOCATION OF THE NEW FRAMING,
 WALLS, DROPPED CEILINGS ETC. FOR WALLS ARE THEY BEARING
 OR NON-BEARING WALLS. PLEASE IDENTIFY THE FRAMING
 MEMBERS BY USAGE, (WALL OR DROPPED CEILING) SIZE OF
 MATERIAL, C-STUDS, JOIST, TRACK, CHANNEL AND OR FURRING
 CHANNEL (HIGH HAT), GAUGE OF MATERIAL/ THICKNESS,
 FLANGE WIDTH, SPACING C/C, FOR WALLS LENGTH OF STUD,
 AND FOR WALLS THE DEFLECTION LIMITATION SEE TABLE
 1604.3.OF THE 2017 FBC-B AND THICKNESS OF DRYWALL, IS
 THE WALL FIRE RATED. FOR DROPPED CEILINGS AND SOFFITS,
 TYPE OF MATERIALS C-STUDS, JOIST, TRACK, CHANNEL AND OR
 FURRING CHANNEL (HIGH HAT), GAUGE OF MATERIAL/
 THICKNESS, FLANGE WIDTH, SPACING C/C, SPAN, MID-POINT
 SUPPORT, THICKNESS OF DRYWALL.
  
 3) THE FLOOR PLAN INDICATES THE INSTALLATION OF WOOD
 AND TILE FLOORING, PLEASE SUBMIT SEPARATE REPORTS FOR
 THE INSULATION UNDERLAYMENT FOR EACH OF THE PRODUCTS,
 WOOD AND TILE FLOORING.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER