Plan Review Notes
Plan Review Notes For Permit 19120251
Permit Number 19120251
Review Stop G
Sequence Number 1
Notes
Date Text
2019-12-10 15:53:4612/10/2019 1ST LP GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF LP GAS.
 A FULL EVALUATION OF ALL GAS EQUIPMENT WILL BE DONE AT
 FIELD, IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO
 CODE COMPLIANCE.
 2. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS,
 BTU?S OF GENERATOR AND REGULATORS (IF NEEDED) ON
 ISOMETRIC PER THE 2017 FBC FG SEC. 409.4.
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 4. SUBMIT COPIES OF THE CORRECT SIZING TABLE USED IN
 THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH
 SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES
 OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF
 THIS SYSTEM IN ACCORDANCE WITH NFPA 58 2014 EDITION.
 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
 7. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND FUTURE BBQ. THEY SHALL BE ONSITE FOR
 FINAL GAS INSPECTION. THE APPLIANCES SHALL BE LISTED
 AND APPROVED. NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL
 MEET THE REQUIREMENTS OF UL 2200.
 8. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF OER THE WPB AMEND. TO FBC SEC. 107.2.1.
 9. IF THE GRILL IS OUTSIDE USE AND IT WILL TO BE IN A
 COVERED PATIO, IF SO PLEASE PROVIDE MANUFACTURES
 RECOMMENDATION FOR A VENTILATION HOOD PER THE 2017 FBC
 RES. SEC. G2408.1.
 10. FUTURE BBQ APPLIANCE CONNECTION SHALL HAVE A VALVE
 AND CAPPED PER THE 2017 RES. SECS. G2415, G2422.1.
 11. THE SUBMITTED THE LOCATION OF THE UNDERGROUND LP
 TANK, INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY.
 THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY
 WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF
 THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE.
 18. I HAVE RESEARCHED CITY RECORDS BACK TO 1999 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 AN LP TANK. WHAT OTHER APPLIANCES/EQUIPMENT IS SUPPLIED
 BY THIS "EXISTING" TANK? SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN
 THIS PERMIT FOR THIS SCOPE OF WORK. WPB AMENDMENTS TO
 THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  