| 2019-12-10 15:53:46 | 12/10/2019 1ST LP GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF LP GAS. |
| | A FULL EVALUATION OF ALL GAS EQUIPMENT WILL BE DONE AT |
| | FIELD, IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO |
| | CODE COMPLIANCE. |
| | 2. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS, |
| | BTU?S OF GENERATOR AND REGULATORS (IF NEEDED) ON |
| | ISOMETRIC PER THE 2017 FBC FG SEC. 409.4. |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | 4. SUBMIT COPIES OF THE CORRECT SIZING TABLE USED IN |
| | THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH |
| | SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES |
| | OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF |
| | THIS SYSTEM IN ACCORDANCE WITH NFPA 58 2014 EDITION. |
| | 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | 7. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR AND FUTURE BBQ. THEY SHALL BE ONSITE FOR |
| | FINAL GAS INSPECTION. THE APPLIANCES SHALL BE LISTED |
| | AND APPROVED. NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL |
| | MEET THE REQUIREMENTS OF UL 2200. |
| | 8. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A |
| | ROOF OER THE WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9. IF THE GRILL IS OUTSIDE USE AND IT WILL TO BE IN A |
| | COVERED PATIO, IF SO PLEASE PROVIDE MANUFACTURES |
| | RECOMMENDATION FOR A VENTILATION HOOD PER THE 2017 FBC |
| | RES. SEC. G2408.1. |
| | 10. FUTURE BBQ APPLIANCE CONNECTION SHALL HAVE A VALVE |
| | AND CAPPED PER THE 2017 RES. SECS. G2415, G2422.1. |
| | 11. THE SUBMITTED THE LOCATION OF THE UNDERGROUND LP |
| | TANK, INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY. |
| | THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY |
| | WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF |
| | THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE. |
| | 18. I HAVE RESEARCHED CITY RECORDS BACK TO 1999 AND |
| | THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| | AN LP TANK. WHAT OTHER APPLIANCES/EQUIPMENT IS SUPPLIED |
| | BY THIS "EXISTING" TANK? SINCE THERE IS NO RECORD OF A |
| | PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN |
| | THIS PERMIT FOR THIS SCOPE OF WORK. WPB AMENDMENTS TO |
| | THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |