| Date |
Text |
| 2020-02-04 14:16:29 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120241 |
| | ADD: 600 NORTHPOINT PARKWAY REMODEL OF THE CORRIDORS |
| | AND PUBLIC SPACES. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ???????????????? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 04/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET UNDER THE HEADING OF CODE |
| | INFORMATION DOES NOT INCLUDE THE 2017 FBC-EXISTING |
| | BUILDING CODE AS PART OF THE CODE DOCUMENTS THE PLANS |
| | WERE CREATED WITH. PLEASE REVIEW THE 2017 FBC-EXISTING |
| | BUILDING CODE SECTION 101.2 SCOPE. THE PROVISIONS OF |
| | THE FLORIDA BUILDING CODE, EXISTING BUILDING SHALL |
| | APPLY TO THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY, |
| | ADDITIONS TO AND RELOCATION OF EXISTING BUILDINGS. |
| | PLEASE UPDATE THE PLANS. |
| | |
| | 2) THE COVER SHEET WITH NOT LISTING THE EXISTING |
| | BUILDING CODE AS ONE OF THE DOCUMENTS THE PLANS WERE |
| | CREATED, THE OTHER ISSUE IS SHOWING COMPLIANCE WITH THE |
| | EXISTING BUILDING CODE SECTION 301.1. THE REPAIRS, |
| | ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS TO AND |
| | RELOCATION OF EXISTING BUILDINGS SHALL COMPLY WITH ONE |
| | OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH |
| | 301.1.3 AS SELECTED BY THE APPLICANT. |
| | 301.1.1. PRESCRIPTIVE COMPLIANCE METHOD. |
| | 301.1.2. WORK AREA METHOD. IF THE WORK AREA METHOD IS |
| | PICKED AT WHAT LEVEL ALTERATION WAS UNDER TAKEN? |
| | 31.1.3. PERFORMANCE METHOD. |
| | 3) PLEASE NOTE THIS PERMIT (19120241) IS STRICTLY FOR |
| | PUBLIC SPACES AND GUEST ROOM CORRIDORS. THE PLANS ARE |
| | SILENT ON THE SAFE GUARDING TENANTS DURING |
| | CONSTRUCTION, THERE IS NO PHASING SHOWN FOR WORK AREAS. |
| | WHEN THE CORRIDORS ARE BEING RENOVATED THERE CAN BE NO |
| | TENANTS IN THE ADJOINING ROOMS. SHOW COMPLIANCE WITH |
| | THE FOLLOWING CODE SECTIONS: |
| | |
| | 3A) 2017 FBC-EXISTING BUILDING SECTION 1501.2 STORAGE & |
| | PLACEMENT. |
| | CONSTRUCTION MATERIALS AND EQUIPMENT SHALL BE STORED |
| | AND PLACED SO AS NOT TO ENDANGER THE PUBLIC, THE |
| | WORKERS OR ADJOINING PROPERTY FOR THE DURATION OF THE |
| | CONSTRUCTION PROJECT. |
| | |
| | 3B) 2017 FBC-EXISTING BUILDING SECTION 1501. 3 |
| | ALTERATIONS & REPAIRS. REQUIRED EXITS, FIRE PROTECTION |
| | DEVICES, AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT |
| | ALL TIMES DURING ALTERATIONS TO ANY BUILDING. |
| | |
| | 3C) 2017 FBC-EXISTING BUILDING SECTION 1501.4. MANNER |
| | OF REMOVAL. WASTE MATERIALS SHALL BE REMOVED IN A |
| | MANNER WHICH PREVENTS INJURY OR DAMAGE TO PERSONS, |
| | ADJOINING PROPERTIES AND THE PUBLIC RIGHT OF WAY. |
| | |
| | 3D) 2017 FBC-EXISTING BUILDING SECTION 1505.2 |
| | MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF |
| | EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING |
| | CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS TO |
| | ANY BUILDING. |
| | |
| | 4) SHEET C105 OWNER SUPPLIED FINISHES SHOWS CARPET, |
| | CARPET PADDING, AND VINYL WALL COVERINGS THE COST OF |
| | THESE MATERIALS NEEDS TO BE ADDED TO THE VALUE OF THE |
| | PROJECT. 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 5A) SHEET C603 & C604 BOTH SHOW THE USE OF CARPET & PAD |
| | OR CARPET IN THE CORRIDORS (EXIT ACCESS) AND VERTICAL |
| | EXIT STAIRS. PLEASE PROVIDE DOCUMENTATION THAT THE |
| | FLOOR COVERING MATERIAL IN ALL OCCUPANCIES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE DOC FF-1 PILL TEST, (CPSC |
| | 16 CFR PART 1630) OR WITH ASTM D2859. |
| | |
| | 5B) PLEASE PROVIDE THE MINIMUM CRITICAL RADIANT FLUX |
| | FOR THE FLOOR COVERINGS. 2017 FBC-B 804.4.2. IN ALL |
| | OCCUPANCIES, INTERIOR FLOOR FINISHES AND FLOOR COVERING |
| | MATERIALS IN ENCLOSURES FOR STAIRWAYS, EXIT |
| | PASSAGEWAYS, CORRIDORS AND ROOMS AND SPACES OR SPACES |
| | NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING |
| | FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL |
| | WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM |
| | RADIANT FLUX SHALL BE NOT LESS THAN CLASS II IN GROUP |
| | A, B, H, I-4, M R-1,R-2 AND S. |
| | |
| | 6) C-106 THE LOBBY FURNITURE PLAN DOES NOT PROVIDE |
| | ELEVATIONS OF THE FOOD COUNTERS, NOR ANY OF THE VARIOUS |
| | TABLES AND CHAIRS IN THE DINING ROOM COMPLIANCE FOR THE |
| | ACCESSIBILITY CANNOT BE REVIEWED. |
| | |
| | 6A ) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 6C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 6D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS |
| | |
| | 6D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |