Plan Review Notes
Plan Review Notes For Permit 19120241
Permit Number 19120241
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-04 14:16:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120241
 ADD: 600 NORTHPOINT PARKWAY REMODEL OF THE CORRIDORS
 AND PUBLIC SPACES.
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 04/2020
 ACTION: DENIED
  
 1) THE COVER SHEET UNDER THE HEADING OF CODE
 INFORMATION DOES NOT INCLUDE THE 2017 FBC-EXISTING
 BUILDING CODE AS PART OF THE CODE DOCUMENTS THE PLANS
 WERE CREATED WITH. PLEASE REVIEW THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 101.2 SCOPE. THE PROVISIONS OF
 THE FLORIDA BUILDING CODE, EXISTING BUILDING SHALL
 APPLY TO THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY,
 ADDITIONS TO AND RELOCATION OF EXISTING BUILDINGS.
 PLEASE UPDATE THE PLANS.
  
 2) THE COVER SHEET WITH NOT LISTING THE EXISTING
 BUILDING CODE AS ONE OF THE DOCUMENTS THE PLANS WERE
 CREATED, THE OTHER ISSUE IS SHOWING COMPLIANCE WITH THE
 EXISTING BUILDING CODE SECTION 301.1. THE REPAIRS,
 ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS TO AND
 RELOCATION OF EXISTING BUILDINGS SHALL COMPLY WITH ONE
 OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT.
 301.1.1. PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2. WORK AREA METHOD. IF THE WORK AREA METHOD IS
 PICKED AT WHAT LEVEL ALTERATION WAS UNDER TAKEN?
 31.1.3. PERFORMANCE METHOD.
 3) PLEASE NOTE THIS PERMIT (19120241) IS STRICTLY FOR
 PUBLIC SPACES AND GUEST ROOM CORRIDORS. THE PLANS ARE
 SILENT ON THE SAFE GUARDING TENANTS DURING
 CONSTRUCTION, THERE IS NO PHASING SHOWN FOR WORK AREAS.
 WHEN THE CORRIDORS ARE BEING RENOVATED THERE CAN BE NO
 TENANTS IN THE ADJOINING ROOMS. SHOW COMPLIANCE WITH
 THE FOLLOWING CODE SECTIONS:
  
 3A) 2017 FBC-EXISTING BUILDING SECTION 1501.2 STORAGE &
 PLACEMENT.
 CONSTRUCTION MATERIALS AND EQUIPMENT SHALL BE STORED
 AND PLACED SO AS NOT TO ENDANGER THE PUBLIC, THE
 WORKERS OR ADJOINING PROPERTY FOR THE DURATION OF THE
 CONSTRUCTION PROJECT.
  
 3B) 2017 FBC-EXISTING BUILDING SECTION 1501. 3
 ALTERATIONS & REPAIRS. REQUIRED EXITS, FIRE PROTECTION
 DEVICES, AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT
 ALL TIMES DURING ALTERATIONS TO ANY BUILDING.
  
 3C) 2017 FBC-EXISTING BUILDING SECTION 1501.4. MANNER
 OF REMOVAL. WASTE MATERIALS SHALL BE REMOVED IN A
 MANNER WHICH PREVENTS INJURY OR DAMAGE TO PERSONS,
 ADJOINING PROPERTIES AND THE PUBLIC RIGHT OF WAY.
  
 3D) 2017 FBC-EXISTING BUILDING SECTION 1505.2
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS TO
 ANY BUILDING.
  
 4) SHEET C105 OWNER SUPPLIED FINISHES SHOWS CARPET,
 CARPET PADDING, AND VINYL WALL COVERINGS THE COST OF
 THESE MATERIALS NEEDS TO BE ADDED TO THE VALUE OF THE
 PROJECT. 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 5A) SHEET C603 & C604 BOTH SHOW THE USE OF CARPET & PAD
 OR CARPET IN THE CORRIDORS (EXIT ACCESS) AND VERTICAL
 EXIT STAIRS. PLEASE PROVIDE DOCUMENTATION THAT THE
 FLOOR COVERING MATERIAL IN ALL OCCUPANCIES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE DOC FF-1 PILL TEST, (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 5B) PLEASE PROVIDE THE MINIMUM CRITICAL RADIANT FLUX
 FOR THE FLOOR COVERINGS. 2017 FBC-B 804.4.2. IN ALL
 OCCUPANCIES, INTERIOR FLOOR FINISHES AND FLOOR COVERING
 MATERIALS IN ENCLOSURES FOR STAIRWAYS, EXIT
 PASSAGEWAYS, CORRIDORS AND ROOMS AND SPACES OR SPACES
 NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING
 FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL
 WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM
 RADIANT FLUX SHALL BE NOT LESS THAN CLASS II IN GROUP
 A, B, H, I-4, M R-1,R-2 AND S.
  
 6) C-106 THE LOBBY FURNITURE PLAN DOES NOT PROVIDE
 ELEVATIONS OF THE FOOD COUNTERS, NOR ANY OF THE VARIOUS
 TABLES AND CHAIRS IN THE DINING ROOM COMPLIANCE FOR THE
 ACCESSIBILITY CANNOT BE REVIEWED.
  
 6A ) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 6C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 6D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS
  
 6D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  