Plan Review Notes
Plan Review Notes For Permit 19120240
Permit Number 19120240
Review Stop B
Sequence Number 3
Notes
Date Text
2020-04-19 08:07:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120240 (INTERIOR REMODEL OF GUEST
 ROOMS)
 ADD: 600 NORTHPOINT PKWY.
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN. APRIL 19TH/2020
  
 ACTION: BUILDING PROVISO
  
 BUILDING PROVISO: THE GENERAL CONTRACTOR SHALL
 COORDINATE PHASING PLAN AND SHALL PROVIDE THE NECESSARY
 DOCUMENTATION RELATED TO PHASING BEFORE CONSTRUCTION
 BEGINS. COPIES OF THE PHASING PLAN ARE TO BE SUBMITTED
 TO THE BUILDING & FIRE DEPARTMENTS. ALL EGRESS AND LIFE
 SAFETY FEATURES SHALL BE MAINTAINED DURING
 CONSTRUCTION. SUBMIT ACTUAL TEST FOR COMPLIANCE WITH
 IIC, STC & FLAME SPREAD REQUIREMENTS FOR FLOOR
 INSULATION UNDER TILE AND OR WOOD LAMINATES.
  
 1) SEE ACTUAL 3RD REVIEW FOR SITE SAFETY REQUIREMENTS
 THAT THE CONTRACTOR IS TO SUBMIT TOTHE BUILDING
 DEPARTMENT BEFORE THE ISSUANCE OF WORK.
  
 2) SUBMIT DOCUMENTATION BEFORE THE START OF
 CONSTRUCTION. CONTRACTOR TO GET THE ARCHITECTS SHOP
 DRAWING STAMP OF APPROVAL FOR THE FLOOR UNDERLAYMENT
 INSULATION BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FLOOR INSULATION (FBC-B 2017) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: PLEASE
 PROVIDE TEST REPORTS (NOT SALES BROCHURES) SHOWING
 COMPLIANCE WITH ALL 3 REQUIREMENTS:
 FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.SHEET
 FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN
 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED
 IN ACCORDANCE WITH ASTM E 90.
 TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  