| 2020-03-31 15:43:30 | |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120240 (INTERIOR REMODEL OF GUEST |
| | ROOMS) |
| | ADD: 600 NORTHPOINT PKWY. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MARCH 31/2020 |
| | ACTION: BUILDING PROVISO |
| | BUILDING PROVISO: THE GENERAL CONTRACTOR SHALL |
| | COORDINATE PHASING PLAN AND SHALL PROVIDE THE NECESSARY |
| | DOCUMENTATION RELATED TO PHASING BEFORE CONSTRUCTION |
| | BEGINS. COPIES OF THE PHASING PLAN ARE TO BE SUBMITTED |
| | TO THE BUILDING & FIRE DEPARTMENTS. ALL EGRESS AND LIFE |
| | SAFETY FEATURES SHALL BE MAINTAINED DURING |
| | CONSTRUCTION. |
| | |
| | |
| | |
| | |
| | |
| | FLOOR INSULATION (FBC-B 2017) FOR TILE, STONE, MARBLE, |
| | VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: PLEASE PROVIDE TEST REPORTS (NOT |
| | SALES BROCHURES) SHOWING COMPLIANCE WITH ALL 3 |
| | REQUIREMENTS: |
| | FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492.SHEET |
| | FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS |
| | AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS |
| | FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL |
| | HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E 90. |
| | TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |