| 2020-02-04 12:56:05 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120240 |
| | ADD: 600 NORTHPOINT PARKWAY INTERIOR REMODEL OF GUEST |
| | ROOMS |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ???????????????? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 04/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET UNDER THE HEADING OF CODE |
| | INFORMATION DOES NOT INCLUDE THE 2017 FBC-EXISTING |
| | BUILDING CODE AS PART OF THE CODE DOCUMENTS THE PLANS |
| | WERE CREATED WITH. PLEASE REVIEW THE 2017 FBC-EXISTING |
| | BUILDING CODE SECTION 101.2 SCOPE. THE PROVISIONS OF |
| | THE FLORIDA BUILDING CODE, EXISTING BUILDING SHALL |
| | APPLY TO THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY, |
| | ADDITIONS TO AND RELOCATION OF EXISTING BUILDINGS. |
| | PLEASE UPDATE THE PLANS. |
| | |
| | 2) THE COVER SHEET WITH NOT LISTING THE EXISTING |
| | BUILDING CODE AS ONE OF THE DOCUMENTS THE PLANS WERE |
| | CREATED, THE OTHER ISSUE IS SHOWING COMPLIANCE WITH THE |
| | EXISTING BUILDING CODE SECTION 301.1. THE REPAIRS, |
| | ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS TO AND |
| | RELOCATION OF EXISTING BUILDINGS SHALL COMPLY WITH ONE |
| | OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH |
| | 301.1.3 AS SELECTED BY THE APPLICANT. |
| | 301.1.1. PRESCRIPTIVE COMPLIANCE METHOD. |
| | 301.1.2. WORK AREA METHOD. IF THE WORK AREA METHOD IS |
| | PICKED AT WHAT LEVEL ALTERATION WAS UNDER TAKEN? |
| | 301.1.3. PERFORMANCE METHOD. |
| | |
| | 3) PLEASE NOTE THIS PERMIT (19120240) IS STRICTLY FOR |
| | ALTERATIONS OF THE GUESTROOMS. PERMIT (19120241) IS FOR |
| | PUBLIC SPACES AND GUEST ROOM CORRIDORS. THE PLANS ARE |
| | SILENT ON THE SAFE GUARDING TENANTS DURING |
| | CONSTRUCTION, THERE IS NO PHASING SHOWN FOR WORK AREAS. |
| | WHEN THE CORRIDORS ARE BEING RENOVATED THERE CAN BE NO |
| | TENANTS IN THE ADJOINING ROOMS. SHOW COMPLIANCE WITH |
| | THE FOLLOWING CODE SECTIONS: |
| | |
| | 3A) 2017 FBC-EXISTING BUILDING SECTION 1501.2 STORAGE & |
| | PLACEMENT. |
| | CONSTRUCTION MATERIALS AND EQUIPMENT SHALL BE STORED |
| | AND PLACED SO AS NOT TO ENDANGER THE PUBLIC, THE |
| | WORKERS OR ADJOINING PROPERTY FOR THE DURATION OF THE |
| | CONSTRUCTION PROJECT. |
| | |
| | 3B) 2017 FBC-EXISTING BUILDING SECTION 1501. 3 |
| | ALTERATIONS & REPAIRS. REQUIRED EXITS, FIRE PROTECTION |
| | DEVICES, AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT |
| | ALL TIMES DURING ALTERATIONS TO ANY BUILDING. |
| | |
| | 3C) 2017 FBC-EXISTING BUILDING SECTION 1501.4. MANNER |
| | OF REMOVAL. WASTE MATERIALS SHALL BE REMOVED IN A |
| | MANNER WHICH PREVENTS INJURY OR DAMAGE TO PERSONS, |
| | ADJOINING PROPERTIES AND THE PUBLIC RIGHT OF WAY. |
| | |
| | 3D) 2017 FBC-EXISTING BUILDING SECTION 1505.2 |
| | MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF |
| | EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING |
| | CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS TO |
| | ANY BUILDING. |
| | |
| | 4) SHEETS R701C, R701D, R703, R703D, R703E & R704B |
| | (ACCESSIBLE BATHROOMS) ALL MAKE REFERENCE TO NOTE 100, |
| | FLOOR TILE. REPLACE AT ACCESSIBLE TUB ROOMS AS REQUIRED |
| | BY TOILET RELOCATION ONLY. ARE THE TOILETS BEING MOVED |
| | TO MAKE ROOM FOR THE REQUIRED CLEAR FLOOR SPACE IN THE |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 604.3.1. THE |
| | PLUMBING SHEET MAKE NO MENTION OF THE WATER CLOSET |
| | BEING MOVED. |
| | |
| | 5) SHEETS R701C, R701D, R703, R703D, R703E & R704B |
| | (ACCESSIBLE BATHROOMS) ALL MAKE REFERENCE TO NOTE 100, |
| | FLOOR TILE, TO BE REPLACED AS REQUIRED BY TOILET |
| | RELOCATION. IF THE WHOLE BATHROOM FLOOR IS BEING |
| | REPLACED THEN COMPLIANCE WITH FLOORING UNDERLAYMENT |
| | MUST BE MET. |
| | |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS: |
| | |
| | 5A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR SLEEPING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492.SHEET |
| | |
| | 5B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS AND SLEEPING UNITS FROM EACH OTHER OR |
| | FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF |
| | FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | |
| | 5C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |