| Date |
Text |
| 2020-01-07 09:36:41 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. |
| | |
| | A)SELF ADHERING ROOF UNDERLAYMENT AS SPECIFIED ON |
| | PLANS. |
| | |
| | B) METAL ROOF PRODUCT APPROVAL: |
| | PLEASE CLEARLY MARK WHICH FASTENING OPTION FROM TABLE |
| | "A" OF PRODUCT APPROVAL SUBMITTED IS GOING TO BE |
| | INSTALLED. THIS IS REQUIRED TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES OF ALL ROOF ZONES. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | ALSO, DRAWINGS SUBMITTED ARE NOT THE OFFICIAL DRAWINGS |
| | THAT WERE APPROVED BY THE FLORIDA BUILDING COMMISSION. |
| | THEY DON'T HAVE THE COPY OF THE ENGINEER OF RECORD SEAL |
| | AND SIGNATURE. PLEASE PROVIDE COPY OF THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND ALL DRAWINGS THAT |
| | CORRESPOND THIS PRODUCT APPROVAL. |
| | FAC 61G20-3.001 |
| | |
| | 2-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | NOTE: PLEASE PROVIDE REVIEW STAMP ON THE FRONT PAGE OR |
| | ON THE FRONT OF ANY PAGE NOT ON THE BACK OF THE PAGE. |
| | THIS WILL FACILITATE THE SCANNING OF THE PRODUCT |
| | APPROVAL FOR FILING PURPOSES. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |