| 2019-12-10 06:37:57 | 12/10/2019 1ST PLUMBING/REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | 2. WASHING MACHINE VALVES SHALL BE ACCESSIBLE WITHOUT |
| | HAVING TO MOVE UNIT 2017 FBC SEC. R2903.3. |
| | 3. VENT FOR WASHING MACHINE NOT SHOWN IN WALL PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 4. TANKLESS HEATER UNIT RHEEM RTEX-11 IS SHOWN OUTSIDE |
| | AND MANUFACTURES INSTALLATION INSTRUCTION STATES THAT |
| | THIS PRODUCT IS DESIGNED TO BE INSTALLED INDOORS ONLY |
| | ON (PAGE 4). IF THE UNIT WILL BE INSIDE MANUFACTURE |
| | RECOMMEND THAT YOU INSTALL A DRIP PAN (CONNECTED TO A |
| | SAFE DRAIN) BELOW THE WATER HEATER TO AVOID PROPERTY |
| | DAMAGE IN THE UNLIKELY EVENT OF A LEAK (ALSO ON PAGE |
| | 4). HTTPS://CDN.GLOBALIMAGESERVER.COM/FETCHDOCUMENT.ASP |
| | X?ID=E0C72D82-1F76-4A55-A7D2-F20611901BD4. PLEASE |
| | PROVIDE A MANUFACTURES SPECIFICATION IF USING ALIENATE |
| | UNIT OR MOVE INSIDE WITH DRAIN PAN AS RECOMMENDED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |