Plan Review Notes
Plan Review Notes For Permit 19120222
Permit Number 19120222
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-10 06:37:5712/10/2019 1ST PLUMBING/REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 2. WASHING MACHINE VALVES SHALL BE ACCESSIBLE WITHOUT
 HAVING TO MOVE UNIT 2017 FBC SEC. R2903.3.
 3. VENT FOR WASHING MACHINE NOT SHOWN IN WALL PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 4. TANKLESS HEATER UNIT RHEEM RTEX-11 IS SHOWN OUTSIDE
 AND MANUFACTURES INSTALLATION INSTRUCTION STATES THAT
 THIS PRODUCT IS DESIGNED TO BE INSTALLED INDOORS ONLY
 ON (PAGE 4). IF THE UNIT WILL BE INSIDE MANUFACTURE
 RECOMMEND THAT YOU INSTALL A DRIP PAN (CONNECTED TO A
 SAFE DRAIN) BELOW THE WATER HEATER TO AVOID PROPERTY
 DAMAGE IN THE UNLIKELY EVENT OF A LEAK (ALSO ON PAGE
 4). HTTPS://CDN.GLOBALIMAGESERVER.COM/FETCHDOCUMENT.ASP
 X?ID=E0C72D82-1F76-4A55-A7D2-F20611901BD4. PLEASE
 PROVIDE A MANUFACTURES SPECIFICATION IF USING ALIENATE
 UNIT OR MOVE INSIDE WITH DRAIN PAN AS RECOMMENDED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  