| 2020-01-07 09:53:27 | RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- REVISE EQUIPMENT LOAD CALCULATIONS. LOAD |
| | CALCULATIONS ARE DONE BASED ON THE FRONT DOOR FACING |
| | NORTH. THIS IS INCORRECT. FRONT DOOR IS FACING SOUTH. |
| | LOAD CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL |
| | ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. 801.3 |
| | FBC-EXISTING BUILDING AND SEC. R403.7.1 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 2- A/C PLAN DOESN'T SHOW ANY TRANSFER DUCT-OR TRANSFER |
| | GRILL ON THE BEDROOM SHOWING COMPLIANCE WITH THE |
| | BALANCED RETURN AIR SEC. M1602.3 FBC-RESIDENTIAL. |
| | PROVIDE COMPLETE INFORMATION. SPECIFY THE TRANSFER DUCT |
| | OR TRANSFER GRILL SIZE. |
| | |
| | 3- THIS BUILDING IS BUILT IN A AE FLOOD ZONE WITH THE |
| | BASE FLOOD ELEVATION OF 12.1 FEET BASED ON NAVD 1988. |
| | THE PROPOSED SCOPE OF WORK IS CONSIDERED SUBSTANTIAL |
| | IMPROVEMENT. |
| | CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2) |
| | FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC. |
| | 18-284 CITY ORDINANCE NO. 4729-17). CLEARLY SPECIFY ON |
| | PLANS THE FINISHED ELEVATION OF THE A/C EQUIPMENT USING |
| | THE NAVD 1988 REFERENCE. NOTE: THE FINISHED FLOOR |
| | ELEVATION NEEDS TO BE AT 14.1 FEET NAVD 1988 OR HIGHER. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |