Plan Review Notes
Plan Review Notes For Permit 19120222
Permit Number 19120222
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-07 09:33:27RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- THIS BUILDING IS BUILT IN A AE FLOOD ZONE WITH THE
 BASE FLOOD BFE: 12.1 FEET BASED ON NAVD 1988. THE
 PROPOSED SCOPE OF WORK IS CONSIDERED SUBSTANTIAL
 IMPROVEMENT.
 CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2)
 FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC.
 18-284 CITY ORDINANCE NO. 4729-17). CLEARLY SPECIFY ON
 PLANS THE FINISHED ELEVATION USING THE NAVD 1988
 REFERENCE. NOTE: THE FINISHED FLOOR ELEVATION NEEDS TO
 BE AT 14.1 FEET NAVD 1988 OR HIGHER.
 IF THE FINISH FLOOR ELEVATION IS BELOW 14.1 FEET NAVD
 1988, THEN ENTIRE HOUSE NEEDS TO BE RAISED. NOTE:
 COORDINATE WITH ITEM #2 BELOW.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED
 FLOOR ELEVATION OF 12.1 FEET NAVD 88. ELEVATION
 CERTIFICATES ARE REQUIRED BASED ON CONSTRUCTION
 DRAWINGS, BUILDING UNDER CONSTRUCTION AND FINISHED
 CONSTRUCTION. PLEASE PROVIDE THE REQUIRED CONSTRUCTION
 DRAWINGS ELEVATION CERTIFICATE TO VERIFY COMPLIANCE
 WITH THE REQUIRED 2 FEET FREEBOARD.
 SEC. 18-284 CITY ORDINANCE NO. 4729-17.
  
 3- THIS IS AN ALTERATION LEVEL 3. PLANS SUBMITTED SHOW
 THAT ALL EXTERIOR WALLS ARE GOING TO BE DEMOLISHED AND
 REBUILT. THIS MEANS THAT ALL WINDOW AND DOORS FRAME
 OPENINGS ARE NEW. NONE OF THE WINDOW SIZES SPECIFIED ON
 THE WINDOW SCHEDULE FOR BEDROOMS #1 AND #2 ON SHEET S-7
 COMPLY WITH THE EGRESS REQUIREMENTS. SINGLE HUNG
 WINDOWS WITH A HEIGHT OF 4'-6"
 DON'T PROVIDE THE 24" MIN. CLEAR HEIGHT OPENING. REVISE
 AS REQUIRED.
 SEC. 505 AND SEC. 801.3 FBC-EXISTING BUILDING.
  
 4- REVISE ENERGY CALCULATIONS. COORDINATE WITH
 ARCHITECTURAL PLANS TO AVOID CONFLICTS/DELAYS:
 A) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, CORRECT
 PERMITTING OFFICE (WEST PALM BEACH NOT PALM BEACH
 COUNTY), AND JURISDICTION NUMBER (THIS JURISDICTION IS
 604700). SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) R-VALUE SPECIFIED ON ITEM #9 ON PAGE 1 OF 5 FOR
 EXTERIOR WALLS DON'T MATCH PLANS. SEE PLANS AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) COOLING AND HEATING INFORMATION SHOWN ON ITEMS #12
 AND #13 ON PAGE 1 OF 5 DOESN'T MATCH INFORMATION SHOWN
 ON PLANS AND LOAD CALCULATIONS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEE SEER AND CAPACITY OF EQUIPMENT.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 F) CLARIFY/REVISE THE "SPACES" INFORMATION ON PAGE 2 OF
 5 WHY THERE ARE NO OCCUPANTS IN THIS HOUSE?. SEC.
 107.2.1 CITY AMENDMENTS AND SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 G) WINDOWS INFORMATION SHOWN ON PAGE 4 OF 5 IS
 INCORRECT. REVISE THE BUILDING ORIENTATION, AND
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEE PLANS
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 A)SELF ADHERING ROOF UNDERLAYMENT AS SPECIFIED ON
 PLANS.
  
 B) GABLE END VENT AS SHOWN ON PLANS.
  
 C) VINYL SOFFIT AS SPECIFIED ON PLANS.
  
 D) EXTERIOR DOOR PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL (2 COPIES), INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO THE DRAWINGS
 SUBMITTED. THE FLORIDA PRODUCT APPROVAL IS REQUIRED
 BECAUSE IT SHOWS IF PRODUCT IS APPROVED AND CURRENT
 CODE IN EFFECT.
  
 E) METAL ROOF PRODUCT APPROVAL:
 PLEASE CLEARLY MARK WHICH FASTENING OPTION FROM TABLE
 "A" OF PRODUCT APPROVAL SUBMITTED IS GOING TO BE
 INSTALLED. THIS IS REQUIRED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF ALL ROOF ZONES. SEC. R301.2.1
 FBC-RESIDENTIAL.
 ALSO, DRAWINGS SUBMITTED ARE NOT THE OFFICIAL DRAWINGS
 THAT WERE APPROVED BY THE FLORIDA BUILDING COMMISSION.
 THEY DON'T HAVE THE COPY OF THE ENGINEER OF RECORD SEAL
 AND SIGNATURE. PLEASE PROVIDE COPY OF THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND ALL DRAWINGS THAT
 CORRESPOND THIS PRODUCT APPROVAL.
 FAC 61G20-3.001
  
 6-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
 NOTE: PLEASE PROVIDE REVIEW STAMP ON THE FRONT PAGE OR
 ON THE FRONT OF ANY PAGE NOT ON THE BACK OF THE PAGE.
 THIS WILL FACILITATE THE SCANNING OF THE PRODUCT
 APPROVAL FOR FILING PURPOSES.
  
 7- SHEET S-1:
 A) REVISE THE FLOOD ZONE SPECIFIED ON THE SITE TABULAR
 DATA. ACCORDING TO THE NEW MAPS IN EFFECT OCTOBER 5,
 2017 THIS PROPERTY IS IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION OF 12.1 FEET NAVD 88. REVISE AS
 REQUIRED.
  
 B) SINGLE FAMILY RESIDENCE IS CLASSIFIED AS R3 NOT R2.
 REVISE TYPICAL NOTE #4 AS REQUIRED. SEC. 310.5
 FBC-BUILDING.
  
 8- REVISE STUCCO THICKNESS SPECIFIED ON ALL DETAILS AND
 SECTIONS.
 NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS NOT
 3/4". SEC. 801.3 FBC-EXISTING BUILDING AND TABLE
 R702.1(1)FBC-RESIDENTIAL.
  
 9- NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE
 BARRIERS. SEC. 801.3 FBC-EXISTING BUILDING AND SEC.
 R703.7.3 FBC-RESIDENTIAL ON THE WOOD FRAMED WALL.
  
 10- WIND LOAD DIAGRAM ON SHEET S-4: THE MINIMUM CORNER
 DISTANCE IS 4'-0" NOT 3'-0".
 SEC. 801.3 FBC-EXISTING BUILDING AND SEE NOTE "A" ON
 FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL SCOPE OF WORK SHOWN ON PLANS.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION TO INCLUDE ALL MATERIALS, LABOR OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES OR PROVIDE COPY
 SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 12- SITE PLAN ON SHEET S-1 AND PALM BEACH COUNTY
 PROPERTY APPRAISER SHOW AN EXISTING SHED. THE PROPERTY
 APPRAISER SHOWS THAT THIS SHED WAS BUILT ON 2019. THIS
 IS A BIG STRUCTURE AND ACCORDING TO CITY RECORDS THERE
 ARE NO PERMITS FOR THE CONSTRUCTION OF THIS BUILDING. A
 BUILDING PERMIT IS REQUIRED FOR THE CONSTRUCTION OF ANY
 STRUCTURE. SEC. 105.1 CITY AMENDMENTS. NEED TO PROVIDE
 COMPLETE DRAWINGS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THIS SHED.
 NOTE: THIS COMMENT WILL NOT AFFECT THE PROCESS OF THE
 PERMIT FOR THE MAIN HOUSE BUT IT WILL NEED TO BE
 ADDRESSED. INFORMATION CAN BE SUBMITTED ALONG WITH THIS
 PERMIT OR IT CAN BE SUBMITTED UNDER A SEPARATE PERMIT.
 PLEASE ADVISE HOW DEALING WITH THIS COMMENT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  