| Plan Review Notes For Permit 19120213 |
| Permit Number |
19120213 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-10 08:15:06 | PLAN DENIED | | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLANS | | | SECTION 107 FBC 2017 | | | 2) PROVIDE CFM ON ALL SUPPLY DUCTS. SECTION | | | 107 FBC 2017 | | | 3) HEATING AND COOLING LOADS REQUIRED.SECTION | | | 312 FBC (M) 2017 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|