| 2020-01-03 14:18:19 | PLAN REVIEW - MECHANICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SERVICE DISCONNECT FOR CU ON PLAN PAGE E.01 SHALL BE |
| | 220 VOLT. |
| | PANEL SCHEDULE: |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 2. INDICATE THE SIZE OF THE RETURN DUCTS FROM THE RAG'S |
| | TO THE AIR HANDLER- SHOW DUCTS ON PLAN. |
| | SECTION M1602.2 FBC RES. |
| | |
| | 3. PROVIDE ENGINEERING FOR INSTALLATION OF THE |
| | CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS |
| | M1305.1.4.1 AND M1401.4 FBC RES. |
| | |
| | 4. PROVIDE LOCKING ACCESS PORT CAPS. |
| | M1411.8 LOCKING ACCESS PORT CAPS. |
| | |
| | 5. PROVIDE ENERGY SUBMITTAL |
| | R405.2 EC. |
| | |
| | 6. PROVIDE MANUAL J WORSHEETS WITH AC SYSTEM SIZING |
| | CALCULATIONS. |
| | SECTION R403.7.1 FBC EC. |
| | |
| | 7. PROVIDE EQUIPMENT SCHEDULE ON PLAN. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. EXHAUST VENTILATION AT A RATE OF 100 CFMS |
| | INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED |
| | FOR THE KITCHEN. |
| | TABLE M1507.4 FBC RES. PLEASE SEE SECTION M1503.1 FOR |
| | RANGE HOOD REQUIREMENTS, AND M1503.4 FOR MAKEUP AIR. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |