| Plan Review Notes For Permit 19120174 |
| Permit Number |
19120174 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-09 16:48:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF CARD READER AT THE EXIT | | | DOOR. | | | | | | THE CARD READER SHALL BE INSTALLED UNDER SEPARATE PEMTI | | | AND SHOP DRAWINGS AND COMPLY WITH NFP 101, CH 7 MEANS | | | OF EGRESS. | | | | | | | | | | | | 2) THERE IS A INDICATION OF FIRE SPRINKLER WORK. | | | | | | ANY WORK ON THE SPRINKLER SYSTEM SHALL BE DONE UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|