| 2020-01-07 10:26:05 | 1) THE EXISTING PLANS ON FILE WITH THE CITY SHOW THIS |
| | SYSTEM AS A NATURAL GAS SYSTEM.ALL APPLIANCES AND |
| | EQUIPMENT SHALL NOT BE USED FOR LP GAS UNLESS IT IS |
| | CONVERTED TO USE LP GAS AND IS TESTED FOR PERFORMANCE |
| | WITH LP GAS BEFORE BEING PLACED INTO USE.PER NFPA 58 |
| | SEC.5.20.2. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1. ALL |
| | REGULATORS FOR OUTDOOR INSTALLATIONS SHALL BE DESIGNED, |
| | INSTALLED, OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| | AFFECTED BY THE ELEMENTS PER NFPA 58 SEC.6.8.1.4. THE |
| | REGULATORS SHALL BE LISTED FOR EXTERIOR USE. |
| | 3) SUBMIT DOCUMENTATION FOR COMPLIANCE WITH THE |
| | REQUIREMENTS OF 2017 FBC-FUEL GAS CODE SEC.301.10 FOR |
| | WIND RESISTANCE. A SHEET HAS BEEN SUBMITTED SHOWING |
| | EYEBOLTS, METAL CABLE AND CLAMPS. ADDITIONAL |
| | DOCUMENTATION IS REQUIRED TO SHOW COMPLIANCE WITH 2017 |
| | FBC-BUILDING SEC.1609.1 FOR WIND LOAD. |
| | 4) COPPER TUBING SHALL BE EITHER TYPE K OR L PER NFPA |
| | 58 SEC.5.9.3.2 (2). |
| | 5) INDICATE ON THE PLANS THE TYPE OF FOUNDATION THAT |
| | THE TANKS ARE RESTING UPON. |
| | 6) INDICATE ON THE PLANS IF THE TANKS WILL BE EXCHANGED |
| | OR IF THEY WILL BE FILLED ONSITE.IF FILLED ONSITE, THE |
| | OPERATIONS SHALL COMPLY WITH CHAPTER 7 OF NFPA 58. |
| | 7) INDICATE ON THE PLANS THE HEIGHT OF THE BOLLARDS |
| | ABOVE GROUND, THE EMBEDMENT DEPTH BELOW GROUND AND THE |
| | TYPE OF MATERIAL FROM WHICH THEY ARE CONSTRUCTED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 8) THE EXISTING GAS PLANS ON FILE WITH THE CITY SHOW A |
| | TOTAL BTU LOAD OF 1,020,000 BUT THE PLAN SUBMITTED FOR |
| | THIS PROJECT NOTE A BTU LOAD OF 500,000 BTU'S. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |