| 2020-03-04 15:35:05 | PLAN REVIEW - BUILDING |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1) CORRECTED |
| | |
| | 2) 107.5.3 FBC[AMENDED] ADD CODE EDITION TO STATE |
| | CURRENT BUILDING CODE THAT APPLIES TO NEW WORK. (2017 |
| | FLORIDA BUILDING CODE 6TH EDITION) (PLACE GOVERNING |
| | CODES ON FLOOR PLAN PAGE) |
| | |
| | 3) CORRECTED |
| | |
| | 4) THE DRAWINGS PROVIDED LACK SOME DETAIL AS TO THE |
| | BUILDING WILL MEET FLORIDA BUILDING CODES. PLEASE SEE |
| | BELOW FOR SOME ADDITIONAL INFORMATION THAT WILL HELP |
| | CLARIFY THE PROPOSED CONSTRUCTION. |
| | A. ADD DIMENSIONS TO THE PLANS THAT WILL AID IN |
| | BUILDING AND DETERMINING SQ. FOOTAGE. (NOT ADDRESSED) |
| | B. PROVIDE WINDOW AND DOOR SCHEDULES TO SHOW WINDOW |
| | LOCATIONS AND SIZES. SCHEDULE CAN CORESPOND WITH MARKS |
| | ON PLAN VIEW. (NOT ADDRESSED) (YOU MAY PLACE ROUGH |
| | OPENINGS AND DESIGN PRESSURES NEXT TO EACH OPENING ON |
| | PLAN) |
| | C. CORRECTED |
| | D. PLANS SAY STRAP AT VARIOUS POINTS IN THE ASSEMBLY. |
| | PLEASE STATE THE TYPE OF STRAP THAT WILL BE USED AT |
| | THESE LOCATIONS. (CANNOT READ CONNECTOR "A" ON |
| | SCHEDULE) |
| | E. CORRECTED |
| | |
| | 5) ASCE 7-10 26.7.1 PLEASE ADD PROJECT DATA TO PLANS. |
| | (NOT CORRECTED) (PLACE THE FOLLOWING INFORMATION ON |
| | FLOOR PLAN PAGE) |
| | |
| | BUILDING TYPE - ACCESSORY |
| | OCCUPANCY = R3 |
| | TYPE OF WALL CONSTRUCTION = WOOD FRAMED |
| | RISK CATEGORY = I |
| | EXPOSURE CATEGORY = B |
| | BUILDING CLASSIFICATION = ENCLOSED |
| | MEAN BLDG. HGT. = 0?-0? THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| | PEAK. (NOT CORRECTED) |
| | WIND SPEED V ULT = 155 |
| | WIND SPEED V ASD = 112 |
| | UNCONDITIONED SPACE = 672 SQ. FT. |
| | |
| | 6) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOORS. (DESIGNER TO SELECT MODEL TO BE |
| | INSTALLED WITH INSTALLATION INSTRUCTIONS) (FLOOR PLAN |
| | INDICATES DOUBLE HUNG WINDOWS - PROVIDE PRODUCT |
| | APPROVALS FOR DOUBLE HUNG WINDOWS. DESIGNER SHALL |
| | SELECT MODEL AND PROVIDE INSTALLATION INSTRUCTIONS) |
| | 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS. |
| | (NOT CORRECTED) |
| | NOTE: R301.2.1.2 STORAGE SHEDS THAT ARE NOT DESIGNED |
| | FOR HUMAN HABITATION AND THAT HAVE A FLOOR AREA OF 720 |
| | SQUARE FEET (67 M2) OR LESS ARE NOT REQUIRED TO COMPLY |
| | WITH THE MANDATORY WIND-BORNE DEBRIS IMPACT STANDARD OF |
| | THIS CODE. |
| | * THIS MEANS THEY DO NOT HAVE TO HAVE HURRICANE |
| | PROTECTION, BUT THEY STILL NEED TO MEET PRESSURES. THE |
| | PRODUCT APPROVALS WILL STATE THE PRESSURES THEY ARE |
| | DESIGNED FOR. |
| | |
| | 7) CORRECTED |
| | |
| | 8) R318 FBC[R]ADD NOTE FOR TERMITE TREATMENT TO BE |
| | COMPLETED AS REQUIRED IN R318. (NOT CORRECTED) |
| | |
| | NEW COMMENTS |
| | |
| | 9) CITY OF WPB CHPT. 1 ? VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | |
| | THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF |
| | WORK. |
| | |
| | THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. |
| | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS |
| | |
| | |
| | |