| 2019-12-24 11:48:48 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | 1) OUTLETS REQUIRED |
| | |
| | E3901.9 BASEMENTS, GARAGES AND ACCESSORY BUILDINGS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET, IN ADDITION TO ANY |
| | PROVIDED FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN |
| | EACH SEPARATE UNFINISHED PORTION OF A BASEMENT, IN EACH |
| | ATTACHED GARAGE, AND IN EACH DETACHED GARAGE OR |
| | ACCESSORY BUILDING THAT IS PROVIDED WITH ELECTRICAL |
| | POWER. THE BRANCH CIRCUIT SUPPLYING THE RECEPTACLE(S) |
| | IN A GARAGE SHALL NOT SUPPLY OUTLETS OUTSIDE OF THE |
| | GARAGE AND NOT LESS THAN ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED FOR EACH MOTOR VEHICLE SPACE. [210.52(G)(1), |
| | (2), AND (3)] |
| | |
| | E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES |
| | INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF |
| | UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK |
| | AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. [210.8(A)(2)] |
| | |
| | 2) LIGHTING REQUIRED. |
| | |
| | E3903.3 ADDITIONAL LOCATIONS. |
| | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED |
| | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT |
| | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL |
| | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR |
| | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL |
| | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED |
| | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A |
| | VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN |
| | OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS |
| | ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A |
| | WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT |
| | INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS |
| | WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE |
| | RISERS. [210.70(A)(2)] |
| | |
| | 3) LOAD CALCULATION REQUIRED FOR THE SERVICE. |
| | |
| | E3704.1CONDUCTOR SIZE. |
| | FEEDER CONDUCTORS THAT DO NOT SERVE 100 PERCENT OF THE |
| | DWELLING UNIT LOAD AND BRANCH-CIRCUIT CONDUCTORS SHALL |
| | BE OF A SIZE SUFFICIENT TO CARRY THE LOAD AS DETERMINED |
| | BY THIS CHAPTER. FEEDER CONDUCTORS SHALL NOT BE |
| | REQUIRED TO BE LARGER THAN THE SERVICE-ENTRANCE |
| | CONDUCTORS THAT SUPPLY THE DWELLING UNIT. THE LOAD FOR |
| | FEEDER CONDUCTORS THAT SERVE AS THE MAIN POWER FEEDER |
| | TO A DWELLING UNIT SHALL BE DETERMINED AS SPECIFIED IN |
| | CHAPTER 36 FOR SERVICES. [310.15(B)(7)(2) AND (3)] |
| | |
| | E3602.2SERVICE LOAD. |
| | THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND |
| | SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING |
| | UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE |
| | E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE |
| | DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE |
| | DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR |
| | FEEDERS IN ACCORDANCE WITH CHAPTER 37. [220.82(A)] |
| | |
| | 4) NO ELECTRIC SHOWN |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |