Plan Review Notes
Plan Review Notes For Permit 19120149
Permit Number 19120149
Review Stop E
Sequence Number 1
Notes
Date Text
2019-12-24 11:48:48FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) OUTLETS REQUIRED
  
 E3901.9 BASEMENTS, GARAGES AND ACCESSORY BUILDINGS.
 NOT LESS THAN ONE RECEPTACLE OUTLET, IN ADDITION TO ANY
 PROVIDED FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN
 EACH SEPARATE UNFINISHED PORTION OF A BASEMENT, IN EACH
 ATTACHED GARAGE, AND IN EACH DETACHED GARAGE OR
 ACCESSORY BUILDING THAT IS PROVIDED WITH ELECTRICAL
 POWER. THE BRANCH CIRCUIT SUPPLYING THE RECEPTACLE(S)
 IN A GARAGE SHALL NOT SUPPLY OUTLETS OUTSIDE OF THE
 GARAGE AND NOT LESS THAN ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED FOR EACH MOTOR VEHICLE SPACE. [210.52(G)(1),
 (2), AND (3)]
  
 E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES
 INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF
 UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK
 AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(2)]
  
 2) LIGHTING REQUIRED.
  
 E3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT
 LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL
 ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED
 GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A
 VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN
 OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS
 ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A
 WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT
 INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS
 WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE
 RISERS. [210.70(A)(2)]
  
 3) LOAD CALCULATION REQUIRED FOR THE SERVICE.
  
 E3704.1CONDUCTOR SIZE.
 FEEDER CONDUCTORS THAT DO NOT SERVE 100 PERCENT OF THE
 DWELLING UNIT LOAD AND BRANCH-CIRCUIT CONDUCTORS SHALL
 BE OF A SIZE SUFFICIENT TO CARRY THE LOAD AS DETERMINED
 BY THIS CHAPTER. FEEDER CONDUCTORS SHALL NOT BE
 REQUIRED TO BE LARGER THAN THE SERVICE-ENTRANCE
 CONDUCTORS THAT SUPPLY THE DWELLING UNIT. THE LOAD FOR
 FEEDER CONDUCTORS THAT SERVE AS THE MAIN POWER FEEDER
 TO A DWELLING UNIT SHALL BE DETERMINED AS SPECIFIED IN
 CHAPTER 36 FOR SERVICES. [310.15(B)(7)(2) AND (3)]
  
 E3602.2SERVICE LOAD.
 THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING
 UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE
 E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37. [220.82(A)]
  
 4) NO ELECTRIC SHOWN
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  
  