| 2020-01-03 15:49:24 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19120149 |
| | REVIEWED: JANUARY 3, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | - PLEASE ADD SIGNATURE OF RESPONSIBLE PARTY TO ALL |
| | PLANS. ALSO, PROVIDE A SECOND SET OF PLANS. |
| | |
| | 2) 107.5.3 FBC[AMENDED] ADD CODE EDITION TO STATE |
| | CURRENT BUILDING CODE THAT APPLIES TO NEW WORK. (2017 |
| | FLORIDA BUILDING CODE 6TH EDITION) |
| | |
| | 3) WILL THIS STRUCTURE BE COOLED? IS SO PLEASE PROVIDE |
| | INSULATION THAT WILL BE USED IN CEILING AND WALLS AND |
| | PROVIDE MECHANICAL PLANS. |
| | IF COOLING OR VENTILATION PROVIDED PROVIDE PLANS AND A |
| | MECHANICAL REVIEW WILL BE ADDED. |
| | |
| | 4) THE DRAWINGS PROVIDED LACK SOME DETAIL AS TO THE |
| | BUILDING WILL MEET FLORIDA BUILDING CODES. PLEASE SEE |
| | BELOW FOR SOME ADDITIONAL INFORMATION THAT WILL HELP |
| | CLARIFY THE PROPOSED CONSTRUCTION. |
| | A. ADD DIMENSIONS TO THE PLANS THAT WILL AID IN |
| | BUILDING AND DETERMINING SQ. FOOTAGE. |
| | B. PROVIDE WINDOW AND DOOR SCHEDULES TO SHOW WINDOW |
| | LOCATIONS AND SIZES. SCHEDULE CAN CORESPOND WITH MARKS |
| | ON PLAN VIEW. |
| | C. R802 FBC[R]SHOW A ROOF PLAN THAT RELATES TO THE |
| | DETAIL PROVIDED. WILL THE ROOF BE ENGINEERED TRUSSES, |
| | OR ARE THEY SITE BUILT. IF SITE BUILT PLEASE SHOW HOW |
| | THEY WILL BE CONNECTED AT AL POINTS AND HOW THEY RESIST |
| | LATERAL FORCES (BRACING AND GABLE END BRACING) |
| | D. PLANS SAY STRAP AT VARIOUS POINTS IN THE ASSEMBLY. |
| | PLEASE STATE THE TYPE OF STRAP THAT WILL BE USED AT |
| | THESE LOCATIONS. |
| | E. ARE THERE VENTS AT THE OVERHANGS? PROVIDE DETIAL OF |
| | OVERHANG AND HOW/WHERE VENTS ARE INSTALLED. |
| | |
| | 5) ASCE 7-10 26.7.1 PLEASE ADD PROJECT DATA TO PLANS. |
| | STATE ON PLAN THAT THIS WILL BE ACCESSORY STRUCTURE. |
| | OCCUPANCY = R3 |
| | TYPE OF WALL CONSTRUCTION = ARE THE WALLS MASONRY, |
| | CONCRETE OR WOOD FRAMED? |
| | RISK CATEGORY = I |
| | EXPOSURE CATEGORY = B |
| | BUILDING CLASSIFICATION = ENCLOSED |
| | MEAN BLDG. HGT. = 0?-0? THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| | PEAK. |
| | WIND SPEED V ULT = 155 |
| | WIND SPEED V ASD = 112 |
| | ALSO, STATE SQ. FOOTAGE CONDITIONED AND NON |
| | CONDITIONED. |
| | |
| | 6) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOORS. |
| | 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS. |
| | NOTE: R301.2.1.2 STORAGE SHEDS THAT ARE NOT DESIGNED |
| | FOR HUMAN HABITATION AND THAT HAVE A FLOOR AREA OF 720 |
| | SQUARE FEET (67 M2) OR LESS ARE NOT REQUIRED TO COMPLY |
| | WITH THE MANDATORY WIND-BORNE DEBRIS IMPACT STANDARD OF |
| | THIS CODE. |
| | * THIS MEANS THEY DO NOT HAVE TO HAVE HURRICANE |
| | PROTECTION, BUT THEY STILL NEED TO MEET PRESSURES. THE |
| | PRODUCT APPROVALS WILL STATE THE PRESSURES THEY ARE |
| | DESIGNED FOR. |
| | |
| | 7) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL FOR |
| | ROOF SHINGLES. |
| | |
| | 8) R308 FBC[R]ADD NOTE FOR TERMITE TREATMENT TO BE |
| | COMPLETED AS REQUIRED IN R308. |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |