| 2019-12-06 12:42:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO FLOOR PLAN, EXITS, LIGHTING, ETC. |
| | ATTACHED TO THIS SUBMITTAL. |
| | |
| | THE PROPOSED TENT IS OF SUCH SIZE THAT A LIFE SAFETY |
| | PLAN IS REQUIRED. |
| | |
| | PER NFPA 101 - CH 12 |
| | |
| | |
| | 12.4.1.4.3 LIFE SAFETY FLOOR PLANS. LIFE SAFETY FLOOR |
| | PLANS OF EACH |
| | LEVEL SHALL BE PROVIDED ? AS APPLICABLE ? WITH THE |
| | FOLLOWING: |
| | (1) OCCUPANT LOAD, EXIT LOCATION, EGRESS CAPACITY, MAIN |
| | ENTRANCE/EXIT, HORIZONTAL EXITS, TRAVEL DISTANCE, AND |
| | EXIT |
| | DISCHARGE |
| | |
| | EVENT PLANS FOR EACH ANTICIPATED TYPE OF EVENT |
| | DEPICTING THE |
| | FOLLOWING: |
| | (A) SEATING CONFIGURATION |
| | (B) EXHIBIT BOOTH LAYOUT |
| | (C) STAGE LOCATION |
| | (D) OCCUPANT LOAD, EGRESS CAPACITY REQUIRED, EXITS |
| | PROVIDED, |
| | AND TRAVEL DISTANCE |
| | (E) ANY FLOOR OR STAGE USE RESTRICTIONS |
| | |
| | 12.7.9.2 UNSECURED SEATING. |
| | 12.7.9.2.1 SEATS NOT SECURED TO THE FLOOR SHALL BE |
| | PERMITTED IN |
| | RESTAURANTS, NIGHT CLUBS, AND OTHER OCCUPANCIES WHERE |
| | FASTENING |
| | SEATS TO THE FLOOR MIGHT BE IMPRACTICABLE. |
| | 12.7.9.2.2 UNSECURED SEATS SHALL BE PERMITTED, PROVIDED |
| | THAT, IN |
| | THE AREA USED FOR SEATING, EXCLUDING SUCH AREAS AS |
| | DANCE FLOORS AND |
| | STAGES, THERE IS NOT MORE THAN ONE SEAT FOR EACH 15 FT2 |
| | (1.4 M2) OF |
| | NET FLOOR AREA, AND ADEQUATE AISLES TO REACH EXITS ARE |
| | MAINTAINED AT |
| | ALL TIMES. |
| | 12.7.9.2.3 SEATING DIAGRAMS SHALL BE SUBMITTED FOR |
| | APPROVAL BY THE |
| | AUTHORITY HAVING JURISDICTION TO PERMIT AN INCREASE IN |
| | OCCUPANT |
| | LOAD PER 7.3.1.3. |
| | |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | |
| | 2) WILL THERE BE ANY GENERATORS OR AIR CONDITIONERS |
| | PROVIDED? |
| | |
| | PROVIDE PROVIDE DETAILS AND LOCATIONS. |
| | |
| | |
| | |
| | 3) WILL ELECTRICAL WIRING AND LIGHTING BE INSTALLED? |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |