| Plan Review Notes For Permit 19120065 |
| Permit Number |
19120065 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-01-24 15:20:34 | GAS 2ND REVIEW**DENIED**19120065 | | | | | | PREVIOUS COMMENTS NOT COMPLIED WITH. PLEASE PROVIDE | | | RESPONSE LETTER. | | | 1) PROVIDE DRIP LEG WITH IN 10 PIPE DIAMETERS OF THE | | | GAS REGULATOR. FBC-GAS 410.2 | | | | | | 3) THE TANK TIE DOWN SHEETS ARE SIGN BY AN ARCHITECT | | | WERE ITS CALLING FOR AN ENGINEER. SHOW WERE AN | | | ARCHITECT HAS THE AUTHORITY TO APPROVED THESE DRAWING | | | WITH IN HIS SCOPE OF LICENSE. FBC 107.2.1 | | | 4) THE SIGN AND SEAL BY THE ARCHITECT IS A COPY. PLAN | | | MUST BE DIGITALLY SIGNED AND SEAL PER FAC 61G1-16.005. | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|