| 2019-12-27 07:39:40 | GAS 1ST REVIEW**DENIED**19120065 | | | 1) PROVIDE DRIP LEG WITH IN 10 PIPE DIAMETERS OF THE | | | GAS REGULATOR. FBC-GAS 410.2 | | | 2) PROVIDE GENERATOR INSTALLATION MANUAL OR APPROVE | | | PERMIT # FOR GENERATOR. FBC 107.3.5 | | | 3) THE TANK TIE DOWN SHEETS ARE SIGN BY AN ARCHITECT | | | WERE ITS CALLING FOR AN ENGINEER. SHOW WERE AN | | | ARCHITECT HAS THE AUTHORITY TO APPROVED THESE DRAWING | | | WITH IN HIS SCOPE OF LICENSE. FBC 107.2.1 | | | 4) THE SIGN AND SEAL BY THE ARCHITECT IS A COPY. PLAN | | | MUST BE DIGITALLY SIGNED AND SEAL PER FAC 61G1-16.005. | | | 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE 1ST AND | | | 2ND STAGE PRESSURE REGULATORS. REGULATORS INSTALLED ON | | | THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR | | | OUTDOOR INSTALLATION. 2017 FGC SEC.410.1 | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|