| Plan Review Notes For Permit 19120063 |
| Permit Number |
19120063 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-12-30 07:39:46 | PLUMBING 1ST REVIEW**DENIED**19120063 | | | 1-PROVIDE A NARRATIVE OF WHAT THIS REVISION ENTAILS. | | | FBC 107.2.1 | | | 2-GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION | | | ONLY. PLEASE REMOVE THE VERTICAL GRAB BAR IN THE TOILET | | | ROOMS. 609.4POSITION OF GRAB BARS. GRAB BARS SHALL BE | | | INSTALLED IN A HORIZONTAL POSITION. | | | 3- WITH THE TOILET PAPER DISPENSER BEING OWNER SUPPLIED | | | PLEASE ADD NOTE THAT MOUNTING TO BE 7?-9? TO THE CENTER | | | OF THE WHERE IT DISPENSER PAPERS 1ST ROLL. FBC-ACC | | | 604.7 | | | 4-SHOW REAR GRAB BAR MOUNTING AS 12? FROM THE CENTER | | | LINE OF THE TOILET AND NOT JUST 6? OFF SIDE WALL. | | | FBC-ACC 604.5.2 | | | 5- PROVIDE A SANITARY AND WATER RISER ISOMETRIC | | | DRAWING. YOU ARE ONLY SHOWING A FLAT DRAWING. FBC | | | 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | | | | | | | | | | |
|