| 2019-12-30 07:38:55 | GAS 1ST REVIEW**DENIED**19120063 |
| | ****PLEASE SUBMIT A NARRATIVE OF THE CHANGES FOR THIS |
| | REVISION**** |
| | 1-GAS INFORMATION IS LISTED DIFFERENTLY ON SHT. CS1 |
| | THEN ON P1.1 AND P2. PIPE SIZE, DISTANCE AND GAS |
| | PRESSURE DOES NOT MATCH. PLEASE CORRECT. FBC 107.3.5 |
| | 2- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 3- SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1 |
| | |
| | 4-. SUBMIT TWO COPIES OF A SIDE VIEW SHOWING THE |
| | MOUNTING OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. WPB AMEND. TO FBC SEC. |
| | 107.2.1 |
| | |
| | 5- SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) |
| | 6- IF 2 POUND GAS SYSTEM SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1 |
| | 7) IF 2 POUND SYSTEM SHOW THE DISTANCE FROM THE 2 PSI |
| | REGULATOR TO THE APPLIANCE. COMPLY WITH 2017 FBC-FUEL |
| | GAS SEC. 402.4.1 |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH (CGA SOLUTIONS) |
| | [email protected] |
| | 561-248-2703 |
| | |
| | |