Plan Review Notes
Plan Review Notes For Permit 19120053
Permit Number 19120053
Review Stop Z
Sequence Number 2
Notes
Date Text
2020-04-02 16:08:33 
 ** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE A SIGNED AND SEALED SURVEY OF THE PROPERTY.
 PLEASE NOTE THAT THE SURVEY (AND ANY OTHER
 DOCUMENTATION) MUST SHOW THAT THE APPLICANT IS THE
 OWNER OF THE PROPERTY AND THE HOLDER OF RIPARIAN
 RIGHTS. [ZLDR S.94-313(A)(2)A.] [1/10/2020 REPEAT
 COMMENT]
  
 2.) PROVIDE A SITE PLAN DRAWN TO SCALE SUFFICIENT TO
 REPRESENT ALL ELEMENTS OF THE PROPOSED DOCK AND OF THE
 RIPARIAN PROPERTY FROM WHICH THE DOCK WILL PROJECT AND
 OF THE ADJACENT PROPERTIES ON BOTH SIDES THEREOF. [ZLDR
 S.94-313(A)(2)C.] [1/10/2020 REPEAT COMMENT]
  
 3.) PROVIDE A CROSS SECTION SHOWING ALL ELEMENTS OF THE
 PROPOSED DOCK, THE BOTTOM OF THE WATERWAY, AS WELL AS
 THE MEAN HIGH WATERLINE AND MEAN LOW WATER LINE. [ZLDR
 S.94-313(A)(2)D.] [1/10/2020 REPEAT COMMENT]
  
 4.) VALID WRITTEN APPROVAL OF THE PROPOSED DOCK BY THE
 FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION (DEP),
 THE U.S. ARMY CORPS OF ENGINEERS (THE CORPS) AND/OR THE
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SFWMD) IS
 REQUIRED. SUCH WRITTEN APPROVAL SHALL CONTAIN THE DATE
 ON WHICH THE PROPOSED DOCK WAS APPROVED. [ZLDR
 S.94-313(A)(2)E.] [1/10/2020 REPEAT COMMENT]
  
 5.) PROVIDE DOCUMENTATION THAT THE PROPOSED DOCK WILL
 COMPLY WITH THE STANDARDS OF ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR) S.94-313(A)(3).
 [1/10/2020 REPEAT COMMENT]
  
 6.) ALL MOORING SLIPS SHALL BE PROVIDED WITH
 APPROPRIATE CONNECTIONS FOR POTABLE WATER AND
 ELECTRICAL SERVICE. [ZLDR S.94-313(A)(3)G.] [1/10/2020
 REPEAT COMMENT]
  
 7.) THE PROPOSED DOCK, TEES, DOLPHINS, PILINGS,
 BOATLIFTS, AND OTHER MOORING-RELATED FACILITIES SHALL
 BE CONSTRUCTED WITHIN THE MIDDLE-ONE THIRD OF THE LOT
 ON WHICH A DOCK IS CONSTRUCTED, AS EXTENDED INTO THE
 WATERWAY. PLEASE PROVIDE DIMENSIONS WITHIN THE SURVEY
 AND SITE PLAN THAT SHOW THE PROPOSED DOCK AND ALL
 RELATED ELEMENTS WILL BE LOCATED WITHIN THE MIDDLE
 ONE-THIRD OF THE LOT. [ZLDR S.94-313(A)(3)H.]
 [1/10/2020 REPEAT COMMENT]
  
 8.) THE PROPOSED BOAT AND JET SKI LIFTS SHALL BE
 DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER. ALL
 LIFTS SHALL BE DESIGNED IN ACCORDANCE WITH CURRENT
 ELECTRICAL CODES AND IN COMPLIANCE WITH ALL
 MANUFACTURERS? SPECIFICATIONS. [ZLDR S.94-313(A)(3)Q.]
 [1/10/2020 REPEAT COMMENT]
  
 9.) ALL DOLPHINS SHALL HAVE REFLECTORIZED BAND OF AT
 LEAST 5 INCHES IN WIDTH AND LOCATED APPROXIMATELY 24
 INCHES FROM THE TOP OF DOLPHIN. REFLECTOR TAPE SHALL BE
 FORMULATED FOR MARINE USE AND BE OF AN IRIDESCENT
 SILVER COLOR. [ZLDR S.94-313(A)(3)R.] [1/10/2020 REPEAT
 COMMENT]
  
 10.) WILL THERE BE A SECURITY FENCE AND/OR STEPS? IF
 SO, PLEASE PROVIDE DETAILS. [1/10/2020 REPEAT COMMENT]
  
  
  
 NOTES:
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
 * MASTER PERMIT: #19020388 (NEW SFR)
  