Plan Review Notes
Plan Review Notes For Permit 19120049
Permit Number 19120049
Review Stop P
Sequence Number 3
Notes
Date Text
2020-02-06 14:59:15PLUMBING COMMENTS: APPROVED W/PROVISO
  
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL TWO (2) COPIES UPDATED ENERGY &
 LOAD CALCULATIONS NOTING THE PROPER JURISDICTION AND
 THE WATER HEATER. DOCUMENT SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR
 OWN RISK.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL TWO (2) COPIES STAMPED AND
 SIGNED BY THE ENGINEER, A SLAB REPAIR DETAIL FOR REVIEW
 AND ONCE APPROVED HAVE TWO COPIES AT THE JOB SITE PRIOR
 TO FIRST INSPECTION. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS
 AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND
 THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
 3. PER FBC PL 1002.1, PROVIDE INDIVIDUAL TRAPPED
 FIXTURE DRAIN FOR EACH COMPARTMENT OF THE
 THREE-COMPARTMENT SINK. SEE REDLINED CORRECTION ON
 SANITARY ISOMETRIC.
 4. NOTE THAT NEW BATHROOM GROUP IS WET VENTED BY THE
 UPSTREAM EXISTING BATHROOM GROUP IN ACCORDANCE WITH FBC
 PL 912.1.
  
  
 19120049 525 CLEMATIS ST
  