Plan Review Notes
Plan Review Notes For Permit 19120049
Permit Number 19120049
Review Stop P
Sequence Number 2
Notes
Date Text
2020-01-28 10:43:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. SECOND REQUEST; PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS AND INSTALLATION GUIDE FOR THE TANKLESS
 WATER HEATER IN ORDER TO VERIFY SIZING, PER WPB AMEND
 TO FBC 107.2.1. PLEASE NOTE THAT THE RTEX-08 NOTED IS
 ONLY CAPABLE OF PRODUCING 1.95 GPM WHICH IS
 INSUFFICIENT FOR THE HOT WATER REQUIREMENTS FOR THE
 PROJECT. ADDITIONALLY, DO NOT SPECIFY
 2. PER WPB AMEND TO FBC 107.2.1, PROVIDE CALCULATIONS
 IN ACCORDANCE WITH FBC PL SECTION 709 AND SECTION 915
 FOR SIZING OF THE COMBINATION WASTE AND VENT SYSTEM FOR
 THE BAR AND DOG RUN. INCLUDE SIZE OF STUDOR VENT(S).
 PER FBC PL 915.2.5, PROVIDE VENT FOR EACH DOG RUN FLOOR
 DRAIN.
 3. NEW BATHROOM APPEARS TO BE DOWNSTREAM FROM EXISTING
 BATHROOM GROUP. PER WPB FBC 107.2.1, CONFIRM THAT ONLY
 THE UPSTREAM BATHROOM GROUP FIXTURES ARE DISCHARGING
 THROUGH THE NEW BATHROOM GROUP COMPLYING WITH THE
 REQUIREMENTS OF FBC PL 912.1 OR VENT THE NEW WATER
 CLOSET AND FLOOR DRAIN WITH THE LAVATORY AS A WET VENT
 BEFORE CONNECTING TO THE BUILDING DRAIN.
 4. SECOND REQUEST; SHOW P-TRAPS AND FIXTURE DRAINS FOR
 3 COMPARTMENT POT SINK AND HAND SINK (SEE COMMENT 15
 FROM REVIEW #1); WATER CLOSET IS INTEGRALLY TRAPPED AND
 SHALL NOT BE PROVIDED WITH AN ADDITIONAL TRAP AS IS
 SHOWN ON THE ISOMETRIC.
 5. SHOW HOT WATER RECIRCULATION SYSTEM INCLUDING PUMP
 ON ISOMETRIC AND PLAN VIEW COMPLYING WITH FBC PL 607.2;
 SPECIFY INSULATION (SEE COMMENT 14 FROM REVIEW #1)).
 PER WPB AMEND TO FBC 107.2.1, PROVIDE MANUFACTURE
 SPECIFICATIONS FOR RECIRCULATION PUMP; PROVIDE SCHEDULE
 AND PUMP DETAIL.
 6. REGARDING ITEM 19; ICE MACHINE, PROVIDE A BACKFLOW
 PREVENTER FOR THE POTABLE WATER SUPPLY PER FBC PL 608.3
 FOR THE ICE MACHINE AND PROVIDE AN INDIRECT WASTE PIPE
 FROM THE UNIT TO A TRAPPED AND VENTED WASTE RECEPTOR
 THROUGH AN AIR GAP COMPLYING WITH FBC PL 802.1.3,
 802.2.1 AND 802.3.
 7. PROVIDE HOSE BIB IN VICINITY OF SOUTH END OF DOG RUN
 TO PROVIDE FOR WASHDOWN.
 8. PER WPB FBC 107.2.1, PROVIDE UPDATED ENERGY & LOAD
 CALCULATIONS NOTING THE PROPER JURISDICTION AND THE
 WATER HEATER.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120049 525 CLEMATIS ST
  