2019-12-27 16:50:061ST REVIEW: 19120049
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WALL FOR THE EXISTING BATHROOM WAS REMOVED
 MAKING THE BATHROOM AN ALTERATION AND SHALL COMPLY WITH
 FBC ACC 213
 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET
 ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH
 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING
 ROOM SHALL COMPLY WITH 603.
 213.3.2 WATER CLOSETS. WHERE WATER CLOSETS ARE
 PROVIDED, AT LEAST ONE SHALL COMPLY WITH 604.
 213.3.4 LAVATORIES. WHERE LAVATORIES ARE PROVIDED, AT
 LEAST ONE SHALL COMPLY WITH 606 AND SHALL NOT BE
 LOCATED IN A TOILET COMPARTMENT.
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,PER FBC PL 609.4
  
 3. SHT A1.2 THE DETAIL FOR THE ADA CLEARANCES AND
 MOUNTING HEIGHTS SHOW A SHOWER AND A URINAL THEY ARE
 NOT SHOWN ON THE PLAN PLEASE CLARIFY.PER WPB AMEND TO
 FBC 107.2.1
  
 4. PROVIDE FLOOR PLAN SHOWING CLEAR FLOOR SPACE FOR THE
 TOILETS AND LAVATORIES SHOW THE DIMENSIONS . PER FBC
 ACC 606.2,604.3.1
  
 5. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 6. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 7. THE PLAN IS CALLING THE OCCUPANCY AS AN A3 BUT IT
 APPEARS MORE LIKE A2 LIKE A BAR PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 8. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE FOR THE TANKLESS WATER HEATER IN
 ORDER TO VERIFY SIZING.PER WPB AMEND TO FBC 107.2.1
  
 9. ON THE SANITARY ISOMETRIC THE TOILET AND FLOOR DRAIN
 IN THE NEW BATHROOM SHALL BE VENTED BEFORE CONNECTING
 TO THE BUILDING DRAIN. THEY CAN BE VENTED BY THE
 LAVATORY TO FORM A WET VENT SYSTEM. PER FBC PL 912.1
  
 10. HOW WILL THE DOG AREA BE DRAINED TO MAINTAIN
 SANITARY CONDITIONS.PER WPB AMEND TO FBC 107.2.1
  
 11. ALL FLOOR DRAINS ARE REQUIRED TO HAVE A TRAP
 PRIMER. PER FBC PL 1002.4.1
  
 12. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 13. PROVIDE A WATER ISOMETRIC.PER WPB AMEND TO FBC
 107.2.1
  
 14. A RECIRCULATION SYSTEM IS GOING TO BE REQUIRED. PER
 FBC PL 607.2
  
 15. SHOW THE P-TRAPS ON THE SANITARY ISOMETRIC DRAWING
 FOR THE FLOOR DRAINS, SINKS PER WPB AMEND TO FBC
 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711