| 2019-12-24 14:58:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #9120049 |
| | 12/24/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| | SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION |
| | 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| | APPLIED IF THE MANUFACTURER'S PERFORMANCE DATA |
| | INDICATES THE AIR HANDLER IS NOT CAPABLE OF PRODUCING |
| | OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 2) M1.1: AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER IS |
| | REQUIRED FOR THE O/A INTAKE SUPPLYING AHU-1- SECTION |
| | C403.2.4.3 FBC EC. |
| | |
| | 3) M1.1: SHOW THE SEQUENCE OF OPERATION FOR EF-2. |
| | |
| | 4) M1.1: PLEASE PLACE A NOTE INDICATING A SEPARATE |
| | PERMIT IS REQUIRED FOR THE WALK-IN COOLER- SECTION |
| | 107.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |