Plan Review Notes For Permit 19120049
Permit Number 19120049
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-04 15:56:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.0 - THIUS APPEARS TO BE A CHANGE OF
 OCCUPANCY. WHAT IS THE EXISTING OCCUPANCY?
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR THE RECORD.
  
  
  
 1A) SHEET A 1.0 - THERE IS AN INDICATION OF AN A3
 OCCUPANCY WITH ON OCCUPANT LOAD OF 30 AND A SQ FT OF
 2940.
  
 REGARDLESS OF THE DOG RUN, HUMANS CAN AND WILL OCCUPY
 THIS SPACE WITH THEIR DOGS, IT IS STILL AN ASSEMBBLY
 OCCUPANCY PER NFPA 101.
  
 PLEASE REVIEW AND CORRECT THE OCCUPANCY LOAD WHILE
 PROVIDING SPECIFIC DIMENSIONS OF THE SEPARATE AREAS..
  
  
  
 1B) SHEET A 1.4 - THERE ARE NO INDICATION OF THE
 ADJACENT OCCUPANCIES NOR FIRE RESISTANCE RATING OF THE
 OCCUPANCY SEPARATION WALLS.
  
 PER NFPA 101, CH 6, OCCUPANCY CLASSIFICATION
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 1.0 - UNDER THE CODE INFORMATION THERE IS AN
 INDICATION OF NFPA 101, 2012.
  
 THE CURRENT EDITION OF NFPA 101 IS 2015.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE WITH ALL
 ASSOCIATED CODES OF THE 6TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE.
  
  
  
 3) SHEET A 1.4 - THERE IS AN INDICATION OF OCCUPANT
 LOAD OF 22 BAR 18 DOG PLAY AREA 8 DETERMINATION BY THE
 FIRE MARSHAL
  
 A. THIS TOTAL DOES NOT THE COVER PAGE AND PER # 1
 ABOVE.
  
 B. I AM THE FIRE MARSHAL AND I DO NOT RECALL THIS
 DETERMINATION.
  
 C. THERE ARE NO INDICATIONS OF SEATING AT THE BAR.
 THERE IS NO BAR LENGHT DIMENSION
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 4) SHEET A 1.2 - THERE IS NO EXIT DOOR HARDWARE
 INDICATED ON THE DOOR SCHEDULE.
  
 EXIT DOOR HARDWARE SHALL COMPLY PER NFPA 101, CH 12
 
 EGRESS.
  
 12.2.2 MEANS OF EGRESS COMPONENTS.
 12.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF
 EGRESS
 SHALL BE LIMITED TO THE TYPES DESCRIBED IN 12.2.2.2
 THROUGH 12.2.2.12.
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC