| 2019-12-04 15:56:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1.0 - THIUS APPEARS TO BE A CHANGE OF |
| | OCCUPANCY. WHAT IS THE EXISTING OCCUPANCY? |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS FOR THE RECORD. |
| | |
| | |
| | |
| | 1A) SHEET A 1.0 - THERE IS AN INDICATION OF AN A3 |
| | OCCUPANCY WITH ON OCCUPANT LOAD OF 30 AND A SQ FT OF |
| | 2940. |
| | |
| | REGARDLESS OF THE DOG RUN, HUMANS CAN AND WILL OCCUPY |
| | THIS SPACE WITH THEIR DOGS, IT IS STILL AN ASSEMBBLY |
| | OCCUPANCY PER NFPA 101. |
| | |
| | PLEASE REVIEW AND CORRECT THE OCCUPANCY LOAD WHILE |
| | PROVIDING SPECIFIC DIMENSIONS OF THE SEPARATE AREAS.. |
| | |
| | |
| | |
| | 1B) SHEET A 1.4 - THERE ARE NO INDICATION OF THE |
| | ADJACENT OCCUPANCIES NOR FIRE RESISTANCE RATING OF THE |
| | OCCUPANCY SEPARATION WALLS. |
| | |
| | PER NFPA 101, CH 6, OCCUPANCY CLASSIFICATION |
| | |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A 1.0 - UNDER THE CODE INFORMATION THERE IS AN |
| | INDICATION OF NFPA 101, 2012. |
| | |
| | THE CURRENT EDITION OF NFPA 101 IS 2015. |
| | |
| | PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE WITH ALL |
| | ASSOCIATED CODES OF THE 6TH EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | |
| | |
| | 3) SHEET A 1.4 - THERE IS AN INDICATION OF OCCUPANT |
| | LOAD OF 22 BAR 18 DOG PLAY AREA 8 DETERMINATION BY THE |
| | FIRE MARSHAL |
| | |
| | A. THIS TOTAL DOES NOT THE COVER PAGE AND PER # 1 |
| | ABOVE. |
| | |
| | B. I AM THE FIRE MARSHAL AND I DO NOT RECALL THIS |
| | DETERMINATION. |
| | |
| | C. THERE ARE NO INDICATIONS OF SEATING AT THE BAR. |
| | THERE IS NO BAR LENGHT DIMENSION |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 1.2 - THERE IS NO EXIT DOOR HARDWARE |
| | INDICATED ON THE DOOR SCHEDULE. |
| | |
| | EXIT DOOR HARDWARE SHALL COMPLY PER NFPA 101, CH 12 |
| | |
| | EGRESS. |
| | |
| | 12.2.2 MEANS OF EGRESS COMPONENTS. |
| | 12.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF |
| | EGRESS |
| | SHALL BE LIMITED TO THE TYPES DESCRIBED IN 12.2.2.2 |
| | THROUGH 12.2.2.12. |
| | 12.2.2.2 DOORS. |
| | 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | |
| | 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. |
| | 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE |
| | EQUIPPED WITH |
| | PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET |
| | ALL OF THE |
| | FOLLOWING CRITERIA: |
| | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE |
| | ACTUATING |
| | PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF |
| | OF THE |
| | WIDTH OF THE DOOR LEAF. |
| | (2) IT SHALL BE MOUNTED AS FOLLOWS: |
| | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. |
| | (865 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 |
| | IN. (760 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE |
| | NOT TO EXCEED |
| | 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND |
| | LATCHES. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |