Plan Review Notes
Plan Review Notes For Permit 19120049
Permit Number 19120049
Review Stop E
Sequence Number 1
Notes
Date Text
2019-12-24 12:54:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IS THERE AN EXISTING SERVICE AT THIS LOCATION THAT
 IS BEING REPLACED? PROVIDE RISER DIAGRAM OF EXISTING
 SERVICE AS WELL AS THE PROPOSED RISER. NEC 215.5; WPB
 FBC 107.2.1
 2. RISER DIAGRAM SHOWS A 120/240 VOLT DELTA SERVICE.
 PROVIDE NOTES FOR REQUIRED MRARKING AND IDENTIFICATION
 OF HIGH-LEG. NEC 110.15
 3. PANEL SCHEDULE SHOWS SINGLE PHASE LOADS ON THE HIGH
 LEG OF THE SYSTEM. PROVIDE CORRECTION. NEC 110.3,
 110.7, 110.8, 408.3(E)(1)
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 5. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 6. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 7. RISER DIAGRAM DOES NOT SHOW THE CORRECT AMOUNT OF
 WIRES FOR A THREE PHASE SUYSTEM. PROVIDE CORRECTION.
 WPB FBC 107.2.1; NEC 215.5, 250.24(C), 408.3
 8. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING
 CONDUCTOR TO PANEL B, WHICH IS A 125 AMP MAIN BREAKER
 PANEL. THIS WIRE IS UNDERSIZED. PROVIDE CORRECTION. NEC
 250.122
 9. RISER DIAGRAM SHOWS PANEL C AS A MAIN LUG PANEL.
 PROVIDE OVERCURRENT PROTECTION AND DISCONNECT FOR THIS
 PANEL. NEC 230.70, 240.4
 10. PANEL SCHEDULE FOR PANEL C SHOWS THE PANEL AS
 SINGLE PHASE, BUT STATES THAT IT IS A DELTA PANEL,
 WHICH IS ONLY A THREE PHASE DESIGNATION. PROVIDE
 CLARIFICATION AND/OR CORRECTION AS NEEDED. NEC 110.3;
 WPB FBC 107.2.1
 11. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 IN BAR AREA. NEC 210.8(B)
 12. FLOOR PLAN SHOWS AN ELECTRICAL PANEL IN THE
 BATHROOM AREAL. PROVIDE CORRECTION. NEC 240.24(E)
 13. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 14. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 15. EXIT AND EMERGENCY LIGHTS SHOULD BE ON THE SAME
 CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 16. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 17. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 18. PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62
  
 END OF COMMENTS.
  
 PLEASE NOTE: THIS PLAN IS SEVERELY LACKING IN REQUIRED
 INFORMATION. THEREFORE, A COMPLETE REVIEW IS NOT
 POSSIBLE AT THIS TIME. SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS. WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RESUBMITTAL
 FORM. ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED
 SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS
 SHOULD REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  