| 2019-12-24 12:54:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. IS THERE AN EXISTING SERVICE AT THIS LOCATION THAT |
| | IS BEING REPLACED? PROVIDE RISER DIAGRAM OF EXISTING |
| | SERVICE AS WELL AS THE PROPOSED RISER. NEC 215.5; WPB |
| | FBC 107.2.1 |
| | 2. RISER DIAGRAM SHOWS A 120/240 VOLT DELTA SERVICE. |
| | PROVIDE NOTES FOR REQUIRED MRARKING AND IDENTIFICATION |
| | OF HIGH-LEG. NEC 110.15 |
| | 3. PANEL SCHEDULE SHOWS SINGLE PHASE LOADS ON THE HIGH |
| | LEG OF THE SYSTEM. PROVIDE CORRECTION. NEC 110.3, |
| | 110.7, 110.8, 408.3(E)(1) |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 |
| | 5. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 7. RISER DIAGRAM DOES NOT SHOW THE CORRECT AMOUNT OF |
| | WIRES FOR A THREE PHASE SUYSTEM. PROVIDE CORRECTION. |
| | WPB FBC 107.2.1; NEC 215.5, 250.24(C), 408.3 |
| | 8. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING |
| | CONDUCTOR TO PANEL B, WHICH IS A 125 AMP MAIN BREAKER |
| | PANEL. THIS WIRE IS UNDERSIZED. PROVIDE CORRECTION. NEC |
| | 250.122 |
| | 9. RISER DIAGRAM SHOWS PANEL C AS A MAIN LUG PANEL. |
| | PROVIDE OVERCURRENT PROTECTION AND DISCONNECT FOR THIS |
| | PANEL. NEC 230.70, 240.4 |
| | 10. PANEL SCHEDULE FOR PANEL C SHOWS THE PANEL AS |
| | SINGLE PHASE, BUT STATES THAT IT IS A DELTA PANEL, |
| | WHICH IS ONLY A THREE PHASE DESIGNATION. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION AS NEEDED. NEC 110.3; |
| | WPB FBC 107.2.1 |
| | 11. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS |
| | IN BAR AREA. NEC 210.8(B) |
| | 12. FLOOR PLAN SHOWS AN ELECTRICAL PANEL IN THE |
| | BATHROOM AREAL. PROVIDE CORRECTION. NEC 240.24(E) |
| | 13. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| | 14. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | 15. EXIT AND EMERGENCY LIGHTS SHOULD BE ON THE SAME |
| | CIRCUIT AS THE LIGHTING IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 16. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63 |
| | 17. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| | CODE. NEC 210.64 |
| | 18. PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: THIS PLAN IS SEVERELY LACKING IN REQUIRED |
| | INFORMATION. THEREFORE, A COMPLETE REVIEW IS NOT |
| | POSSIBLE AT THIS TIME. SUBMITTAL OF ADDITIONAL AND/OR |
| | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| | COMMENTS. WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER |
| | ADDRESSING EACH ITEM ALONG WITH THE CITY RESUBMITTAL |
| | FORM. ADDITIONALLY, INSERT CORRECTED PAGES INTO THE |
| | ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED |
| | SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS |
| | SHOULD REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |