| 2020-01-02 16:39:56 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19120049 |
| | REVIEWED: JANUARY 2, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 601 TABLE FBC[B]SHEET A1.0 STATES CONSTRUCTION TYPE |
| | AS TYPE III. IS THIS TYPE IIIA OR IIIB? |
| | -PLEASE STATE CONSTRUCTION TYPE AND APPLY FIRE |
| | RESISTANCE REQUIREMENTS FOR ELEMENTS AS LISTED IN TABLE |
| | 601. |
| | |
| | 2) 303.3 FBC[B]PLEASE REVIEW YOUR OCCUPANCY ON SHEET |
| | A1.0. THE AREA SERVING DRINKS WOULD BE CONSIDERED A-2. |
| | THE DOG RUN AREA MAY STAY UNDER A-3 AS CLOSEST |
| | OCCUPANCY. |
| | ALSO, SHOW SQ. FOOTAGE AND OCCUPANT LOAD FOR EACH |
| | OCCUPANCY AND AREA. |
| | |
| | 3) 1010.1.10 FBC[B]ADD HARDWARE TO BE USED ON EGRESS |
| | DOORS TO THE DOOR SCHEDULE ON SHEET A1.2. |
| | |
| | 4) 107.3.4.1 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR |
| | NEW WINDOWS AND MULL BAR IF BEING USED, OR INDICATE |
| | THAT THIS WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 5) 226.1 FBC[A] THE ACCESSIBILITY CODE REQUIRES 0.05 % |
| | OF ALL SEATING TO BE ACCESSIBLE. WHERE DINING SURFACES |
| | ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT |
| | LEAST 0.05 PERCENT OF THE SEATING SPACES AND STANDING |
| | SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. |
| | - SHOW ON PLANS 0.05% OF SEATING TO COMPLY WITH 226.1 |
| | AND 902. |
| | - PROVIDE DETAILS TO SHOW HOW THE BAR MEETS 226.1 |
| | |
| | 6) 404.2.4 FBC[A] MANEUVERING CLEARANCES. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS. |
| | -SHOW CLEAR SPACE AT INTERIOR SIDE OF EXISTING BATHROOM |
| | THAT HAS BEEN RECONFIGURED. 48 INCHES NEEDED BETWEEN |
| | DOOR AND CLOSET WHERE WATER HEATER IS BEING LOCATED. |
| | |
| | 7) 107.3.5 FBC[AMENDED]PLEASE PROVIDE DETAILS OF HOW |
| | INTERIOR PARTIONS ARE CONNECTED TO THE FLOOR AND THE |
| | CEILING. |
| | HOW DOES THE CEILING AND EXTERIOR WALL MEET |
| | PRESCRIPTIVE ENERGY CODE? |
| | |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |