| 2019-12-20 14:41:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902 |
| | 2. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 3. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENER. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 4. ONLY ONE SERVICE PER ADDRESS IS PERMITTED, UNLESS |
| | ONE OF THE EXCEPTIONS IS MET. PROVIDE CORRECTION AND/OR |
| | CLARIFICATION. WPB FBC 107.2.1; NEC 230.2; FBC RE |
| | E3601.2 |
| | 5. PROVIDE RISER DIAGRAM OF EXISTING SERVICE THIS WILL |
| | BE FED FROM. NEC 215.5; WPB FBC 107.2.1 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 |
| | 7. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, |
| | 225.32 |
| | 9. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE |
| | RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR |
| | PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| | COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON |
| | THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |