| 2019-12-23 15:28:38 | 1ST REVIEW 19111313 |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA BUILDING CODE PLUMBING 2017 6TH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THIS RESIDENTIAL UNIT WAS BUILT IN COMPLIANCE WITH |
| | THE FAIR HOUSING ACT AND IS REQUIRED TO STAY IN |
| | COMPLIANCE PLEASE INDICATE ON THE PLAN THE DESIGN SPEC |
| | THE BATHROOM IS BEING DESIGNED TO A OR BEACH |
| | SHOW THE CLEAR FLOOR SPACE FOR THE TOILET SHOWER AND |
| | LAVATORY AND THE HIGHT OF THE LAVATORY VANITY AND THE |
| | BACKING FOR GRAB BARS PER THE FAIR HOUSING ACT DESIGN |
| | MANUAL REQUIREMENTS 6+7 PGS. 6.3-6.7, 7.35, 7.43, 7.47, |
| | 7.56 IF THE UNIT IS NOT BEING DESIGNED IN COMPLIANCE TO |
| | FAIR HOUSING PROVIDE A LETTER FROM THE DESIGNER OF |
| | RECORD AND THE UNIT OWNER ACKNOWLEDGING THAT FACT AND |
| | STATING THAT IF THE UNIT IS SOLD IT IS THE |
| | RESPONSIBILITY OF THE OWNER TO BRING THE UNIT BACK INTO |
| | COMPLIANCE. |
| | |
| | 2. THE STUDOR VENTS SHALL NOT BE USED BELOW THE 4TH |
| | BRANCH INTERVAL OF THE SANITARY STACK BELOW THE TOP OF |
| | THE STACK. PER FBC PL 918.3.1 |
| | |
| | 3. PROVIDE A WATER ISOMETRIC. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 4. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION |
| | GUIDE FOR TANKLESS WATER HEATER. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |