| 2019-12-19 10:06:35 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19111287 |
| | 12/19/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A0.02 & M5.2: IT APPEARS THAT FIRE DAMPERS |
| | ARE MISSING WHERE THE O/A DUCT AND OTHER AIR |
| | DISTRIBUTION DUCTS ARE PENETRATING FIRE-RATED DEMISING |
| | WALLS SEPARATING THE OFFICE SUITES.- SECTION 607.5.2 |
| | FBC M. |
| | |
| | 2) M5.2: PLEASE PLACE A NOTE TO INDICATE WHERE THE O/A |
| | DUCT FOR THE FLOOR IS CONNECTING TO THE MAIN TRUNK- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) M5.3: PROVIDE A THROUGH PENETRATION FIRESTOPPING |
| | DETAIL FOR THE CONDENSER WATER PIPING PENETRATING THE |
| | FIRE-RATED SEPARTION WALLS- SECTION 714.3.1 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |