Plan Review Notes
Plan Review Notes For Permit 19111287
Permit Number 19111287
Review Stop M
Sequence Number 1
Notes
Date Text
2019-12-19 10:06:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19111287
 12/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0.02 & M5.2: IT APPEARS THAT FIRE DAMPERS
 ARE MISSING WHERE THE O/A DUCT AND OTHER AIR
 DISTRIBUTION DUCTS ARE PENETRATING FIRE-RATED DEMISING
 WALLS SEPARATING THE OFFICE SUITES.- SECTION 607.5.2
 FBC M.
  
 2) M5.2: PLEASE PLACE A NOTE TO INDICATE WHERE THE O/A
 DUCT FOR THE FLOOR IS CONNECTING TO THE MAIN TRUNK-
 SECTION 107.2.1 WPB.
  
 3) M5.3: PROVIDE A THROUGH PENETRATION FIRESTOPPING
 DETAIL FOR THE CONDENSER WATER PIPING PENETRATING THE
 FIRE-RATED SEPARTION WALLS- SECTION 714.3.1 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  