| 2019-12-20 10:05:35 | 1ST REVIEW 19111231 |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA BUILDING CODE PLUMBING 2017 6TH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE VENTS ON THE WATER CLOSET AND MOP SINK ARE |
| | HORIZONTAL DRY VENT WHICH ARE NOT ALLOWED A VENT MUST |
| | RISE VERTICALLY TO A POINT ABOVE THE FLOOD LEVEL RIM OF |
| | THE FIXTURE THE VENT ON THE WATER CLOSET IS NOT |
| | REQUIRED IT WILL BE VENTED BY THE LAVATORY AS PART OF |
| | THE WET VENT SYSTEM. PER FBC PL 905.3, 905.4 |
| | |
| | 2. THE WATER FOUNTAIN AND MOP SINK SHALL CONNECT TO |
| | BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER |
| | FBC PL 012.1 |
| | |
| | 3. PROVIDE DETAIL SHOWING CLEAR FLOOR SPACE FOR TOILET |
| | AND LAVATORY WITH DIMENSIONS CLEAR FLOOR SPACE SHALL |
| | EXTEND UNDER FIXTURES. PER FBC ACC 606.2, 604.3.1, |
| | 305.5, 305.3 |
| | |
| | 4. SHOW WATER FOUNTAIN COMPLIANCE WITH FBC ACC 602.2, |
| | 602.4, 602.7, PER FBC PL TABLE 403.1 |
| | |
| | 5. IN THE NOTES ON THE WATER ISOMETRIC FOR THE BACKFLOW |
| | AND EXPANSION TANK THESE ARE REQUIRED DEVISE PLEASE |
| | REMOVES THE TEXT ONLY IF NEEDED. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |