| 2019-12-20 10:40:25 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19111231 |
| | 12/20/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M.0.100: PROVIDE AN EXHAUST SYSTEM FOR THE |
| | FITTING ROOM- SEE TABLE 403.3.1.1 FBC M. |
| | |
| | 2) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE NEW |
| | RTU'S- SECTION 107.2.1 WPB. |
| | |
| | 3) PROVIDE ENGINEERING FOR INSTALLATION OF THE CURBS |
| | AND RTU'S- SECTION 301.15 FBC M. |
| | |
| | 4) M.0.200: INDICATE HOW O/A FOR THE RTU'S WILL BE |
| | AUTOMATICALLY CONTROLLED- SEE SECTION C403.2.4.3 FBC M. |
| | |
| | 5) PLEASE INCLUDE THE HVAC DATA IN THE COMCHECK ENERGY |
| | COMPLIANCE REPORT- SECTION C101.5 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |