2019-12-20 10:40:251ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19111231
 12/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.0.100: PROVIDE AN EXHAUST SYSTEM FOR THE
 FITTING ROOM- SEE TABLE 403.3.1.1 FBC M.
  
 2) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE NEW
 RTU'S- SECTION 107.2.1 WPB.
  
 3) PROVIDE ENGINEERING FOR INSTALLATION OF THE CURBS
 AND RTU'S- SECTION 301.15 FBC M.
  
 4) M.0.200: INDICATE HOW O/A FOR THE RTU'S WILL BE
 AUTOMATICALLY CONTROLLED- SEE SECTION C403.2.4.3 FBC M.
  
 5) PLEASE INCLUDE THE HVAC DATA IN THE COMCHECK ENERGY
 COMPLIANCE REPORT- SECTION C101.5 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  