| 2019-11-30 08:35:37 | PLAN REVIEW - BUILDING |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. VALUE HAS BEEN ADJUSTED FRO 85000 TO 180405 BASED ON |
| | THE ICC BUILDING VALUATION TABLES. |
| | |
| | 2. PROVIDE SURVEY AND DRAINAGE PLAN. |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| | COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| | |
| | PROVIDE SITE PLAN. |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED ON A BOUNDARY LINE SURVEY. |
| | |
| | 3. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH |
| | OPENINGS AND DESIGN PRESSURES. |
| | FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND |
| | EXTERIOR DOORS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| | |
| | 5. DESIGNER SHALL STATE INSULATION R VALUES ON PLAN. |
| | CEILINGS R-30 AND WALLS R-3.0. |
| | R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE). |
| | IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1, |
| | INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF |
| | SECTIONS R402.2.1 THROUGH R402.2.13. |
| | |
| | 6. INSULATION ABOVE ATTIC SCUTTLE SHALL EQUAL |
| | SURRONDING R VALUE. |
| | R402.2.4 ACCESS HATCHES AND DOORS. |
| | |
| | 7. ATTIC SCUTTLE SHALL HAVE WEATHER STRIPPING. |
| | R402.2.4 ACCESS HATCHES AND DOORS. |
| | |
| | 8. LANSCAPE PLAN PAGE L INDICATES A THREE FOOT OVERHANG |
| | FOR ROOFING. NO STRUCTURAL DETAILS ARE PROVIDED. PLEASE |
| | CLARIFY. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. SHOW LOCATION OF ATTIC ACCESS ON PLANS. ACCESS SHALL |
| | COMPLY WITH M1305.1.3. SWITCHED LUMINARE AND SERVICE |
| | OUTLET ARE REQUIRED FOR MECH. EQUIPT. IN ATTICS. |
| | M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, |
| | INSERT CORRECTED PAGES INTO |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS |
| | DETACHED. |
| | |
| | |
| | |
| | |
| | |