Plan Review Notes
Plan Review Notes For Permit 19111213
Permit Number 19111213
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-11-27 12:58:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) INSTALL, TEST AND INSPECT PER NFPA 24, STANDARD FOR
 THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES, 2013 EDITION.
  
  
 2) INSTALL SHALL BE COMPLETED BY A LICENSED FLORIDA
 UNDERGROUND FIRE PROTECTION CONTRACTOR.
  
  
 3) PROVIDE ALL PRODUCT AND MATERIALS MANUFACTURES SPEC
 AND INSTALLATION SHEETS FOR REVIEW AND VERIFICATION BY
 FIRE INSPECTOR ON INSPECTION.
  
  
 4) DO NOT COVER OVER PRIOR TO INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  